E5GN-Q1TD AC/DC24 Omron, E5GN-Q1TD AC/DC24 Datasheet - Page 16

CONTROL TEMP DGTL VOLT OUT 24V

E5GN-Q1TD AC/DC24

Manufacturer Part Number
E5GN-Q1TD AC/DC24
Description
CONTROL TEMP DGTL VOLT OUT 24V
Manufacturer
Omron
Type
Digital Temperature Controllerr

Specifications of E5GN-Q1TD AC/DC24

Analog / Digital
Digital
Control Method
ON/OFF
Voltage Rating
24 VAC, 24 VDC
Mounting
Panel
Display Type
11-Segment, 4 Digit
Size
99 mm x 48 mm x 35 mm
Features
Compatible with Support Software (CX-Thermo version 4.2 or higher)
Input Type
Thermocouple
Output Type
Voltage
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.2%
Output Voltage Max
13.8VDC
Output Voltage Min
10.2VDC
Meter Function
Thermocouple
Thermocouple Type
J, K, T, E, L, U, N, R, S, B, W, PLII
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E5GNQ1TDACDC24
Z3048
E54-CT1
Current Transformers
E54-CT3
E54-CT3 Accessory
• Armature
• Plug
Approx. 6 dia.
Approx. 3 dia.
Waterproof Packing
Y92S-32 (for DIN 48 × 24)
(22)
18
25
40 × 40
15
Connection Example
10
3
Plug
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site. Consider one year a rough standard.
OMRON shall not be liable for the level of water resistance if the customer does not perform
periodic replacement.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
30
40
30
15
30
21
5.8 dia.
Two, M3 (depth: 4)
12 dia.
Two, 3.5 dia.
Armature
10.5
Lead
2.36 dia.
2.8
7.5
9
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for the
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
100 mV
100 mV
100 µV
100 µV
100 V
100 V
10
10
10
10
10
10
1
1
1
1
1
1
50 Hz
50 Hz
10
10
100 mA
100 mA
500 Ω
1 kΩ
1 kΩ
1
1
RL = 10 Ω
100 Ω
Thru-current (Io) A (r.m.s.)
Thru-current (Io) A (r.m.s.)
50 Ω
R
100 Ω
L
10
10
= 10 Ω
1%
E5GN
Distortion
factor 10%
3%
100 1,000 A
100 1,000 A
1%
3%
Distor-
tion
factor
10%
16