E5CN-Q2MT-500 AC100-240 Omron, E5CN-Q2MT-500 AC100-240 Datasheet - Page 9

CONTROL TEMP DIGITAL HEAT/COOL

E5CN-Q2MT-500 AC100-240

Manufacturer Part Number
E5CN-Q2MT-500 AC100-240
Description
CONTROL TEMP DIGITAL HEAT/COOL
Manufacturer
Omron
Series
E5CN-Tr
Type
Temperature Controller, Digitalr
Datasheet

Specifications of E5CN-Q2MT-500 AC100-240

Input Type
RTD, Thermocouple (Multiple)
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Output Type
Voltage
Supply Voltage
100 ~ 240VAC
Size
48mm W x 48mm H (1/16 DIN)
Features
Terminal Cover
Display Type
4 Digit (2)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Communications
-
Other names
E5CN-Q2MT-500-AC100240
E5CNQ2MT500AC100240
Z2410
Characteristics
*1. The indication accuracy of K thermocouples in the 200 to 1300 C range, T and N thermocouples at a temperature of 100 C max., and U
*2. Ambient temperature: 10 C to 23 C to 55 C, Voltage range: 15% to 10% of rated voltage
*3. K thermocouple at 100 C max.: 10 max.
*4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is C or F.
*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).
*6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time.
*7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket.
Indication accuracy
Influence of temperature *2
Influence of voltage *2
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Affect of signal source
resistance
Insulation resistance
Dielectric strength
Vibration
resistance
Shock
resistance
Weight
Degree of
protection
Memory protection
Setup Tool
Setup Tool port
Standards
EMC
and L thermocouples at any temperatures is 2 C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400 C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800 C range is 3 C max. The indication accuracy of the R and S
thermocouples at a temperature of 200 C max. is 3 C 1 digit max. The indication accuracy of W thermocouples is 0.3 of PV or 3 C,
whichever is greater, 1 digit max. The indication accuracy of PL II thermocouples is 0.3 of PV or 2 C, whichever is greater,
The P3GA-11 is not certified for UL listing.
Malfunction
Destruction
Malfunction
Destruction
E5CN
E5CN-U
E5CN
E5CN-U
Approved
standards *7
Conformed
standards
http://www.ia.omron.com/
Thermocouple: *1
Platinum resistance thermometer input:
Analog input:
CT input:
Thermocouple input (R, S, B, W, PL II):
Other thermocouple input: *3
Platinum resistance thermometer input:
Analog input:
250 ms
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s) *5
0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
Thermocouple: 0.1 C/ max. (100
Platinum resistance thermometer: 0.1 C/
20 M
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
10 to 55 Hz, 20 m/s
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
100 m/s
300 m/s
Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Front panel: IP50, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.0 or higher
Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1
USB-Serial Conversion Cable is required to connect the computer to the E5CN. *6
UL 61010-1, CSA C22.2 No. 1010-1
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EMS:
ESD Immunity:
Electromagnetic Field Immunity:
Burst Noise Immunity:
Conducted Disturbance Immunity:
Surge Immunity:
Power Frequency Magnetic Field Immunity:
Voltage Dip/Interrupting Immunity:
1999 to 9999 (decimal point position depends on input type)
Terminal block models (E5CN): ( 0.3% of indicated value or 1 C, whichever is greater) 1 digit max.
Plug-in models (E5CN-U): ( 1% of indicated value or 2 C, whichever is greater) 1 digit max.
Terminal block models (E5CN) and plug-in models (E5CN-U): ( 0.2% of indicated value or 0.8 C, whichever is greater) 1 digit
max.
Terminal block models (E5CN) and plug-in models (E5CN-U): 0.2% FS 1 digit max.
Terminal block models (E5CN): 5% FS 1 digit max.
Terminal block models (E5CN): ( 1% of PV or 10 C, whichever is greater) 1 digit max.
Plug-in models (E5CN-U): ( 2% of PV or 10 C, whichever is greater) 1 digit max.
Terminal block models (E5CN): ( 1% of PV or 4 C, whichever is greater) 1 digit max.
Plug-in models (E5CN-U): ( 2% of PV or 4 C, whichever is greater) 1 digit max.
Terminal block models (E5CN) and plug-in models (E5CN-U):
( 1% of PV or 2 C, whichever is greater) 1 digit max.
Terminal block models (E5CN) and plug-in models (E5CN-U): ( 1%FS) 1 digit max.
min. (at 500 VDC)
2
2
, 3 times each in X, Y, and Z directions
, 3 times each in X, Y, and Z directions
2
for 10 min each in X, Y, and Z directions
max.)
max. (10
EN 61326
EN 55011 Group 1, class A
EN 61326
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
max.)
(c)Copyright OMRON Corporation 2008 All Rights Reserved.
E5CN/E5CN-U
1 digit max.
9