Set Point Selection
RUN/STOP Selection
7-1-1 Set Point Selection
7-1-2 RUN/STOP Selection (E5AJ-jB, E5EJ-jB)
46
Event Input Function
Displays the set point
currently selected.
Display level 0
The E5jJ-jB with an event input function is operated with ease with external
relay signal selection.
It is possible to select one of the set points previously set for control operation.
It is possible to enable the E5AJ-jB and E5EJ-jB to RUN or STOP.
Select the set point by opening or short-circuiting event input 1 (EV1). Refer to
the following table. No set point can be selected with key operation.
The following illustration shows the operation of the E5jJ-jB with its EV1 ter-
minal short-circuited (i.e., set point 1 is selected).
The set point on display level 0 and that on display level 1 are synchronized. In
the above example, if the set point on display level 0 is changed from 200 C to
250 C, the set point 1 value on display level 1 will also change to 250 C.
RUN or STOP operation is selected by opening or short-circuiting event input 2
(EV2). Refer to the following table. RUN or STOP operation cannot be selected
with key operation.
When the E5jJ stops operating, its control output will be 0% and fuzzy self-tun-
ing will stop but its alarm output will operate normally.
The operation of the E5jJ the moment the E5jJ is turned on is determined by
the condition of event input 2.
Open
Short-circuited
Open
Short-circuited
EV1
COM
Short-circuit
EV1
EV2
Set point 0
(SP0)
Set point 1
(SP1)
Set point 2
(SP2)
Set point 3
(SP3)
Set point 0 and 1 (2 and 3) set
in advance on display level 1.
SP2 and SP3 can be displayed
only when the set point selec-
tion is selected with the event
input 2 selection (set to RUN/
STOP before shipping) on the
engineering level. Refer to Sec-
tion 9 Engineering Level Set-
tings for details.
Set point 0 (SP0)
Set point 1 (SP1)
RUN
STOP
Set point to be selected
Operation