AM 1601-7RG POWER ONE, AM 1601-7RG Datasheet - Page 6

AM 1601-7RG

Manufacturer Part Number
AM 1601-7RG
Description
Manufacturer
POWER ONE
Type
Non-Inv/StpUp/StpDwnr
Datasheet

Specifications of AM 1601-7RG

Output Current
2A
Input Voltage
15V
Output Voltage
24V
Output Power
50
Screening Level
Commercial
Operating Temperature Min Deg. C
-25C
Operating Temperature Max Deg. C
71C
Product Length (mm)
168.5mm
Product Depth (mm)
111.2mm
Product Height (mm)
38.7mm
Mounting Style
Din-Rail
Pin Count
11
Number Of Outputs
1
Lead Free Status / RoHS Status
Compliant
Input Fuse
A fuse holder containing a slow-blow type fuse (size: 5 × 20
mm) is mounted in the back plate of the converter. The fuse
protects the converter against severe defects. It may not fully
protect it at input voltages exceeding 200 VDC. In applications,
where the converters operate at DC source voltages above
200 VDC, an external fuse or a circuit breaker at system level
should be installed.
The fuse and a VDR form together with the input filter an
effective protection against high input transients.
Table 3: Fuse types (slow-blow)
Fig. 2
Typical input current versus relative input voltage at
nominal output load
BCD20018 Rev AB
Series
AM1000 – 3000
BM1000 – 3000
FM1000 – 3000
CM1000 – 3000
DM1000 – 3000
EM1000 – 3000
LM1000 – 3000
Note: For applications, where the fuse should not be accessible;
see Option F.
1.0
0.1
10
I
i
[A]
1
2
3
Schurter type
SPT 10 A /250 V
SPT 8 A /250 V
SPT 5 A /250 V
SPT 3.15 A /250 V
SPT 2.5 A /250 V
®
4
5
04014a
6
Part number
0001.2514
0001.2513
0001.2511
0001.2509
0001.2508
________
BM
AM
FM
CM
DM
EM
LM
V
i min DC
V
i DC
Page 6 of 26
Input Under-/Overvoltage Lockout
If the input voltage remains below 0.8 V
1.1 V
output(s). When checking this function the absolute maximum
input voltage rating V
table Input data).
Reverse Polarity
Reverse polarity at the input of AM, BM, CM, DM, and FM
models will cause the fuse to blow. In EM and LM models a
series diode will protect the converter. A series diode is not
incorporated in AM, BM, CM, DM and FM types to avoid
unwanted power losses.
Inrush Current
The CM, DM, EM, and LM (excluding FM) models incorporate
an NTC resistor in the input line, which (during the initial
switch-on cycle) limits the peak inrush current in order to
prevent the connectors and switching devices from damage.
Subsequent switch-on cycles within a short interval will cause
an increase of the peak inrush current due to the warming-up
of the NTC resistor. Refer to Option E.
Fig. 3
Typical inrush current at initial switch-on. V
nominal output load
Note: When V
level, the output voltage may be below the value defined in table
Output data.
LM A-EM
80
70
60
50
20
10
40
30
50 Watt DC-DC and AC-DC Converters
I
i
i max
[A]
400
350
300
250
100
200
150
50
0
, an internally generated inhibit signal disables the
0
i
0.2
0.5
is between V
BM
AM
FM
0.4
1.0
i abs
0.6
1.5
must be carefully considered (see
i min
LM
EM
DM
CM
M Series Data Sheet
0.8
2.0
and the undervoltage lockout
1.0
2.5
i min
www.power-one.com
1.2
3.0
or exceeds approx.
i max
1.4
3.5
04015a
(DC) and
1.6
4.0
t [ms]
A-EM
LM

Related parts for AM 1601-7RG