DS1200-3 ARTESYN, DS1200-3 Datasheet - Page 53

no-image

DS1200-3

Manufacturer Part Number
DS1200-3
Description
AC/DC Power Supply Single-OUT 12V 98.4A 1.2KW 30-Pin
Manufacturer
ARTESYN
Datasheet

Specifications of DS1200-3

Input Voltage
90 to 264 V
Output Voltage
12 V
Maximum Current Rating
15(rms) A
Maximum Output Current
98.4 A
Number Of Outputs
1
Maximum Output Power
1200 W
Efficiency
89(Min) %
Input Frequency
47 to 63 Hz
Operating Temperature
-10 to 70 °C
DS1200-3 Series Supported PMBus
Command
Code
7Ah
7Bh
7Ch
7Dh
7Eh
Command Name
STATUS_VOUT
b7
b6
b5
b4
b3
b2
b1
b0
STATUS_IOUT
b7
b6
b5
b4
b3
b2
b1
b0
STATUS_INPUT
b7
b6
b5
b4
b3
b2
b1
b0
STATUS_TEMPERATURE
b7
b6
b5
b4
b3:0
STATUS_CML
b7
b6
b5
b4
b3
b2
b1
b0
TM
Command List:
Default Value
-
-
-
-
Access
Type
R
R
R
R
R
Bytes
Data
1
1
1
1
1
Format
Data
Output voltage related faults and warnings
VOUT Over--voltage Fault
VOUT Over-voltage warning
VOUT Under-voltage Warning
VOUT Under-voltage Fault
VOUT_MAX Warning, an attempt has been
made to set output to a value higher that the
highest permissible voltage.
TON_MAX_FAULT
TOFF_MAX Warning
reserved
Output Current related faults and warnings
IOUT Over current Fault
IOUT Over current And Low Voltage shutdown
Fault
VOUT Under-voltage Warning
VOUT Under-voltage Fault
VOUT_MAX Warning, an attempt has been
made to set output to a value higher that the
highest permissible voltage.
TON_MAX_FAULT
TOFF_MAX Warning
reserved
Input related faults and warnings
VIN Overvoltage Fault
VIN Overvoltge Warning
VIN Undervoltage Warning
VIN Undervoltage Fault
Unit is OFF for insufficient Input Voltage
IIN Overcurrent Fault
IIN Overcurrent Warning
PIN overpower Warning
Temperature related faults and warnings
Overtemperature Fault
Overtemperature Warning
Undertemperature Warning
Undertemperature Fault
reserved
Communications, Logic and Memory
Invalid or unsupported Command Received
Packet Error Check Failed
Memory Fault Detect, CRC Error
Description
Rev.10.03.30_#0.1
DS1200-3 Series
Page 53

Related parts for DS1200-3