AC38B OPTO 22, AC38B Datasheet - Page 11

Computers, Interface Cards

AC38B

Manufacturer Part Number
AC38B
Description
Computers, Interface Cards
Manufacturer
OPTO 22
Datasheet

Specifications of AC38B

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Features
High-Speed RS485 Repeater, 220VAC
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
DATA SHEET
Form 519-100915
RS-485 SERIAL LINE TERMINATION AND BIASING
Two groups of jumpers are provided which are used to connect terminating and biasing resistors. The group labeled H0 - H8 is used to configure
the host RS-485 port while the group labeled R0 - R5 is used to configure the remote RS-485 port. The function of each jumper is as follows:
Jumper H0: Pull-up for host IRQ + line.
Jumper H1: Terminator for host IRQ lines.
Jumper H2: Pull-down for host IRQ - line.
Jumper H3: Pull-up for host TX/RX + line.
Jumper H4: Terminator for host TX/RX lines
Jumper H5: Pull-down for host TX/RX - line.
Jumper H6: Pull-up for host RX + line.
Jumper H7: Terminator for host RX lines.
Jumper H8: Pull-down for host RX - line.
RS-485 communication links must be terminated at both ends and biased at only one place. When using a G4LC32 RS-485 serial port, biasing
is done automatically when terminators are installed.
When using the AC38 as a simple, 2-wire repeater located at the end of both RS-485 links, jumpers H0, H1, H2, H4, H6, H7, H8, and all remote
port jumpers, R0 - R5, should be installed. If biasing is needed on the host link, jumpers H3 and H5 should be installed.
When using the AC38 as an RS-232 to RS-485 converter, all host and remote port jumpers should be installed.
When the AC38 is used anywhere except the end of a link, the appropriate jumpers should be removed to disconnect terminating and biasing
resistors.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800)TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • E-mail: sales@opto22.com
ADAPTER CARDS
Jumper R4: Terminator for remote TX/RX lines.
Jumper R5: Pull-down for remote TX/RX - line.
Jumper R1: Terminator for remote IRQ lines.
Jumper R3: Pull-up for remote TX/RX + line.
Jumper R2: Pull-down for remote IRQ - line.
Jumper R0: Pull-up for remote IRQ + line.
TRADITIONAL
STANDALONE
page 11/14