E5-648-C2421 EATON CUTLER HAMMER, E5-648-C2421 Datasheet

no-image

E5-648-C2421

Manufacturer Part Number
E5-648-C2421
Description
PRESET COUNTER, 6-DIGIT, 90VAC TO 260VAC
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of E5-648-C2421

No. Of Digits / Alpha
6
Digit Height
9mm
Supply Voltage Range
90VAC To 260VAC
Power Consumption
750VA
Counting Speed
50kHz
Operating Temperature Range
-20°C To +65°C
Instruction leaflet IL05407002E
Effective October 2010
E5-648-C242x
electronic preset counter
with two presets

Related parts for E5-648-C2421

E5-648-C2421 Summary of contents

Page 1

... Instruction leaflet IL05407002E E5-648-C242x electronic preset counter with two presets Effective October 2010 ...

Page 2

... Pulse counter . . . . . . . . . . . . . . . . . . . 6 7 .8.5 Tacho/frequency meter . . . . . . . . . . . . 8 7 .8.6 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7 .9.1 Setting via decade keys . . . . . . . . . . 13 7 .9.2 Setting with Teach-In function . . . . . 13 7 .9.3 Setting the tracking presets . . . . . . . 13 E5-648-C242x electronic preset counter with two presets Description 8. Error message . . . . . . . . . . . . . . . . . . . . . . 13 9. Connections . . . . . . . . . . . . . . . . . . . . . . . . 13 9 ...

Page 3

... E5-648-C242x electronic preset counter with two presets 1. preface Please read this instruction manual carefully before installation and start-up. Please observe all warnings and advice, both for your own safety and for general plant safety. If the device is not used in accordance with this instruction manual, then the intended protection can be impaired ...

Page 4

... Enter the main menu by pressing the Prog/Mode key 7.2 Choice of main menus The menus are selected using the keys T2 (next) and T1 (back) 7.3 Entering a sub-menu The sub-menu is opened with the Prog/Mode key and the first menu item is displayed E5-648-C242x with two presets or . (for timed signal). ...

Page 5

... E5-648-C242x electronic preset counter with two presets 7.4 Selecting the menu items The Prog/Mode key is used to select a menu item within the sub-menu 7.5 Setting the menu items The T2 key is used to select the individual settings for the menu items When setting count values, each decade has a key assigned to it ...

Page 6

... See also 7 .9 When the MPI input is activated, the preset counter will be set to the value specified in the parameter SEtPt. See also 7 .10 E5-648-C242x with two presets ...

Page 7

... E5-648-C242x electronic preset counter with two presets Lock input When the Lock input is activated, the programming is inhibited When the Lock input is activated, the setting of the preset values is inhibited When the Lock input is activated, the setting of the preset values and the programming are both inhibited 7 ...

Page 8

... MPI input is deactivated. Internally the frequency meter continues running When the MPI input is activated, the current frequency for the preset that has just been selected will be adopted as the new preset value. See also 7 .9 E5-648-C242x with two presets ...

Page 9

... E5-648-C242x electronic preset counter with two presets Lock input When the Lock input is activated, the programming is inhibited When the Lock input is activated the setting of the preset values is inhibited When the Lock input is activated the setting of the preset values and the programming are both inhibited 7 ...

Page 10

... Automatic reset to zero when main counter = preset value 2 Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when batch counter ≥ preset 1 Manual reset sets both counters to zero electrical reset sets only main counter to zero E5-648-C242x with two presets ...

Page 11

... E5-648-C242x electronic preset counter with two presets Count mode SUBTRACTING with automatic reset and Batch counter Output 2 (timed signal) active when main counter = zero Automatic reset to preset 2 when main counter = zero Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when batch counter ≥ ...

Page 12

... Duration of timed signal of output 1, programmable from 00.01 to 99.99s. Timed output is post-triggered Active: Relay is activated when the preset value is reached. Passive: Relay becomes de-energized when the preset value is reached. E5-648-C242x with two presets ...

Page 13

... E5-648-C242x electronic preset counter with two presets 7.9 Setting the presets 7.9.1 Setting via decade keys In programming mode preset 2 will always be displayed in the lower line. This is except for the output operations AddBat, SubBat, AddTot and SubTot. Press the Prog/Mode key until the preset to be changed is displayed— ...

Page 14

... Hours: 0.001h–999 999h • Function h.min.s: 00h.00min.01s–99h.59min.59s • Output 1 Min. time measurable: 500 µs • Measuring error: <50 ppm • Output 2 Response time of the outputs • Relays: <13 ms • Supply voltage Supply voltage E5-648-C242x electronic preset counter with two presets ...

Page 15

... E5-648-C242x electronic preset counter with two presets 10.5 Signal and control inputs Polarity: programmable NPN/PNP for all inputs in common • Input resistance: 5 kohms • Pulse shape: any • Switching level with AC supply: • HTL level: Low: 0–4 Vdc, High: 12–30 Vdc • ...

Page 16

... Instruction leaflet IL05407002E Effective October 2010 11. Scope of delivery Preset counter • Mounting clip • Instruction manual • 12. ordering codes E5-648-C242 x supply voltage 260 Vac Vdc 13. Frequencies (typical) 13.1 Pulse counter HTL level AC supply • Typ. Low: 2.5V • Typ. High: 22V • ...

Page 17

... E5-648-C242x electronic preset counter with two presets 14. input modes: pulse counting Diagram a Function p = preset Cnt.Dir INP A INP ADD P P+1 SUB Up.Dn INP A INP ADD P P+1 SUB Up.Up INP A INP ADD Quad INP A INP ADD P P+1 SUB Quad 2 INP A INP ADD ...

Page 18

... E5-648-C242x electronic preset counter with two presets pnp: count on rising edge npn: count on falling edge A 90° B Inp A: Count input Count on rising and on falling edges Inp B: Count input Count on rising and on falling edges, Reverse direction Add: Display 0 --> Preset Sub: Display Preset -> ...

Page 19

... E5-648-C242x electronic preset counter with two presets 15. input modes: timing Function Diagram InA.InB INP A INP GATE 0 ADD P SUB InB.InB INP B T1 off GATE 0 ADD P SUB FrRrun off GATE T1 0 ADD P SUB Auto off GATE RESET PRESET ADD P P SUB T2 off ...

Page 20

... 100 E5-648-C242x electronic preset counter with two presets pnp: count on rising edge npn: count on falling edge Inp A: Frequency input Inp B: no function Inp A: Frequency input 1 Inp B: Frequency input 2 Formula: A–B Inp A: Frequency input 1 Inp B: Frequency input 2 Formula 90° B Inp A: Frequency input 1 ...

Page 21

... E5-648-C242x electronic preset counter with two presets 17. output operations Diagram t t Mode only in the mode and Add RESET PR2 PR1 COUNTER t OUT OUT P2 AddAr RESET PR2 PR1 COUNTER t t OUT P1 t OUT P2 AddBat RESET PR2 COUNTER PR1 BATCH OUT P1 t OUT P2 ...

Page 22

... Instruction leaflet IL05407002E Effective October 2010 18. Dimensional drawings (mm) 48 Figure 2. Dimensions 45 +0.6 Figure 3. Panel cut-out 22 eaton corporation www.eaton.com max. 10.5 15.5 4.25 91 E5-648-C242x electronic preset counter with two presets 7 ...

Page 23

... E5-648-C242x electronic preset counter with two presets notes: Instruction leaflet IL05407002E Effective October 2010 eaton corporation www.eaton.com 23 ...

Page 24

Effective October 2010 Eaton Corporation Electrical Sector 1111 Superior Ave. Cleveland, OH 44114 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL05407002E / Z9871 October 2010 electronic preset counter with two ...