NSH5-232UL-3M Omron, NSH5-232UL-3M Datasheet - Page 65

no-image

NSH5-232UL-3M

Manufacturer Part Number
NSH5-232UL-3M
Description
3m RS232 Cable For NSH5
Manufacturer
Omron
Datasheet

Specifications of NSH5-232UL-3M

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Troubleshooting
Memory Cards
The system settings (set in the System Setting using the CX-Designer) are
not changed for the upload operation.
If an error occurs while data is being transferred, a transfer error screen will be
displayed. Check the following items for the messages that are displayed.
After checking the message, reset the PT and transfer the data again. If the
PT system has been damaged due to the power being turned OFF while a file
is being written, it may not be possible to use normal downloading to replace a
system program.
If the system program cannot be replaced or has been corrupted, and the PT
will not start, refer to 3-5-3 Replacing the System Program and replace the
system program using the information provided there.
Memory Card Error
Could not recognize the Memory
Card. Check the Memory Card
and reset the PT.
Project Transmission Error
Transmission failed. Check the
Memory Card and reset the PT.
System Transmission Error
Transmission failed. Check the
Memory Card and reset the PT.
Project Transmission Error
The project cannot be transferred
because it does not match.
System Transmission Error
The system cannot be transferred
because the hardware does not
match.
Cannot find source data. Continue
downloading/uploading?
Error message
Is a Memory Card inserted into the PT?
Is the Memory Card damaged?
Was the Memory Card removed during data
transfer?
Is there insufficient free space on the Memory
Card?
Is the Memory Card damaged?
Does the screen volume exceed the memory
capacity of the PT?
Do the NS-series, NSH5-series, and NSJ-series
projects, systems, and PT models match for the
transmission source and destination?
Does the transfer source directory or file exist?
(Note: If the Yes Button is pressed and data is
transferred, the previous data at the transfer des-
tination will be deleted.)
Items to check
Section 3-5
43

Related parts for NSH5-232UL-3M