H5CX-AS-N AC100-240 Omron, H5CX-AS-N AC100-240 Datasheet - Page 33

Scrw Term,Trans OUT,Multi-Fnct

H5CX-AS-N AC100-240

Manufacturer Part Number
H5CX-AS-N AC100-240
Description
Scrw Term,Trans OUT,Multi-Fnct
Manufacturer
Omron
Series
H5CXr
Datasheets

Specifications of H5CX-AS-N AC100-240

Relay Type
Integrated
Function
Programmable (Multi-Function)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Transistor
Voltage - Supply
100 ~ 240VAC
Mounting Type
Panel Mount
Termination Style
Screw Terminal
Timing Adjustment Method
DIP Switches
Timing Initiate Method
Input Voltage, Trigger Signal
Timing Range
0.001 s to 9999 Hrs
Supply Voltage
100 V to 240 V
Current Rating (max)
100 mA
Display Type
4 Digit LCD Backlight
Product
Digital Timer
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Circuit
-
Contact Rating @ Voltage
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
H5CXASNAC100240
Z3002
Specifications
Ratings
*1. Inrush current will flow for a short time when the power supply is turned ON.
*2. The display is lit only when the power is ON.
• H5CX Digital Timers with 6-digit Display, 2-stage Setting,
• Times the daily operating hours of machinery and tools,
• Easy-to-read backlit negative LCD with 6 digits (displays
• The 2-stage settings and forecast output are ideal for
Classification
Ratings
Mounting method
External connections
Degree of protection
Digits
Time range
Timer mode
Inputs
Reset system
Power reset
Reset voltage
Sensor waiting time
Outputs
Display
Memory backup
Operating temperature range
Storage temperature range
Operating humidity range
Case color
Attachments
and Forecast Output (DIN 48 x 48-mm)
predicting and notifying when maintenance is required.
to 99999.9 h).
maintenance applications.
Inrush Current (Reference Values)
12 to 24 VDC
Voltage
Power supply voltage
Operating voltage
fluctuation range
Power consumption
Input signals
Input method
Signal, reset, gate
Output modes
Output type
Digital Timer H5CX-B@-N
Applied voltage
26.4 VDC
Digital Timer with 6-digit display, 2-stage setting, and forecast output
12 to 24 VDC
90% to 110% rated supply voltage
Approx. 2.3 W
Flush mounting
Screw terminals
IEC IP66, UL508 Type 4X (indoors) for panel front surface only and only when Y92S-29 Waterproof Packing is used
6 digits
0.01 s to 9999.99 s, 1 s to 99 h 59 min 59 s, 0.1 min to 99999.9 min, 0.1 h to 99999.9 h
Elapsed time (Up)
Signal, reset, gate
No-voltage Input
Voltage Input
No-voltage (NPN) input/voltage (PNP) input (switchable)
Minimum input signal width: 1 or 20 ms (selectable, same for all input)
Power resets (only for A mode), external and manual reset
Minimum power-opening time: 0.5 s (except for F-1 mode)
10% max. of rated supply voltage
250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
A, F-1
Transistor output: NPN open collector, 100 mA at 30 VDC max. residual voltage: 1.5 VDC max. (Approx. 1 V)
Leakage current: 0.1 mA max.
7-segment, negative transmissive LCD;
Present value: 10-mm-high characters, red
Set value: 6-mm-high characters, green
EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
-10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or condensation)
-25 to 70°C (with no icing or condensation)
25 to 85%
Black (N1.5)
Waterproof packing, flush mounting adapter, unit label
Inrush current (peak value)
*1
4.4 A
ON impedance
ON residual voltage : 3 V max.
OFF impedance
High (logic) level
Low (logic) level
*2
: 1 kΩ max. (Leakage current: 12 mA when 0 Ω)
: 100 kΩ min.
: 4.5 to 30 VDC
: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
1.7 ms
Time