H3DS-SL AC24-230/DC24-48 Omron, H3DS-SL AC24-230/DC24-48 Datasheet - Page 8

17.5mm TIMER DIN. MNT.

H3DS-SL AC24-230/DC24-48

Manufacturer Part Number
H3DS-SL AC24-230/DC24-48
Description
17.5mm TIMER DIN. MNT.
Manufacturer
Omron
Series
H3DSr
Datasheets

Specifications of H3DS-SL AC24-230/DC24-48

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC, 24 ~ 48VDC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage, Trigger Signal
Timing Range
0.1 s to 120 Hrs
Supply Voltage
24 V to 230 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3DSSLAC24230DC2448
Z2395
Operation
■ Basic Operation
Setting of Selector
The selectors can be turned clockwise and counterclockwise to
select the desired time scale, or operating mode.
Each selector has a snap mechanism that secures the selector at a
given position. Set the selector at a position at which it is secured. Do
not set it midway between two securing positions or a malfunction
could result from improper setting.
Selection of Operating Mode (except
for H3DS-AL)
The H3DS-ML/-SL can be set to any one of the operating modes A to
J. Turn the operating mode selector with a screwdriver until the
desired operating mode appears in the operating mode display win-
dow.
H3DS-ML (8 modes): A, B, B2, C, D, E, G, J
H3DS-SL (4 modes): A, E, B2, J, E, E, J, J
Note: Letters that appear more than once indicate exactly the same
Selection of Time Scale
The time scale is selected by turning the time scale selector. The
time scales will appear in the following order in the time scale display
window on the left of the selector:
1 s, 0.1 s, 1 h, 0.1 h, 10 h, 1 h, 1 m, 0.1 m.
Note: The time scale “1h” appears twice. Both instances indicate ex-
operating mode.
actly the same time scale.
Time scale display
window and selector
(In order of appearance)
(In order of appearance)
http://www.ia.omron.com/
Operating mode display
window and selector
Locking/Unlocking of Selectors and
Time Setting Dial
The time setting dial, time scale selector, and operating mode selec-
tor can be locked using the Y92S-38 Lock Key, a special pen type
tool that is sold separately. To lock the dial or selectors, insert the
Lock Key in the keyhole to the lower right of the dial or selector and
turn it clockwise until the dial or selector is completely covered with
the red cover. To unlock, turn the Lock Key in the opposite direction.
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3DS-M/-S/-A
Key hole
8