E5CN-HQ2M-500 AC100-240 Omron, E5CN-HQ2M-500 AC100-240 Datasheet - Page 10

no-image

E5CN-HQ2M-500 AC100-240

Manufacturer Part Number
E5CN-HQ2M-500 AC100-240
Description
High Function 1/16Din Volt Out
Manufacturer
Omron
Datasheet

Specifications of E5CN-HQ2M-500 AC100-240

No. Of Digits / Alpha
5
Meter Function
Temperature Controller
Meter Range
-200°C To +2300°C
Supply Voltage Range
100VAC To 240VAC
Rohs Compliant
Yes
Nomenclature
E5CN-H
Dimensions
E5CN-H
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ1
48 × 48
Operation indicators
Waterproof
Packing
(Accessory)
58
USB connector (type A plug)
Level Key
6
1.5
Mounting Adapter
(Accessory)
Note: The terminal block cannot be removed.
78
250
OUT1
OUT2
91
SUB1
SUB2
SUB3
HA
Temperature unit
STOP
CMW MANU
Mode Key
Terminal Cover
(E53-COV17)
(Accessory)
44.8 × 44.8 48.8
Down Key
LED indicator
(SD)
E5CN-H
60 min.
Mounted Separately
(2,100)
No. 1 display
No. 2 display
Up Key
LED indicator (RD)
45
+0.6
0
45
Panel Cutout
+0.6
0
• Recommended panel thickness is 1 to
• Group mounting is not possible in the
• To mount the Controller so that it is
• When two or more Controllers are mounted,
5 mm.
vertical direction. (Maintain the specified
mounting space between Controllers.)
waterproof, insert the waterproof packing
onto the Controller.
make sure that the surrounding
temperature does not exceed the allowable
operating temperature specified in the
specifications.
(48 × number of units − 2.5)
1,765
Group mounting does not
allow waterproofing.
Group Mounted
E5CN-H
Serial connector
(Unit: mm)
+1.0
0
45
+0.6
0
10

Related parts for E5CN-HQ2M-500 AC100-240