E5CN-HQ2M-500 AC100-240 Omron, E5CN-HQ2M-500 AC100-240 Datasheet

no-image

E5CN-HQ2M-500 AC100-240

Manufacturer Part Number
E5CN-HQ2M-500 AC100-240
Description
High Function 1/16Din Volt Out
Manufacturer
Omron
Datasheet

Specifications of E5CN-HQ2M-500 AC100-240

No. Of Digits / Alpha
5
Meter Function
Temperature Controller
Meter Range
-200°C To +2300°C
Supply Voltage Range
100VAC To 240VAC
Rohs Compliant
Yes
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive
Maintenance Function.
Main I/O Functions
• High-resolution display with 5 digits/0.01°C display in a compact
• High-speed sampling cycle of 60 ms.
• High Accuracy
• Universal inputs on all models (thermocouple, PT, or analog input)
• A PV/SV-status display function can be set to automatically alternate
• Flexible contact outputs with logic operations (AND, OR, and
• Preventive maintenance for relays in the Temperature Controller
Advanced Digital Temperature Controller
E5CN-H
Controller (48 x 48 mm).
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
to handle various sensors with one Controller.
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
delays) set from the Support Software (CX-Thermo Ver. 4.0)
using a Control Output ON/OFF Counter.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
Indication Accuracy
• Thermocouple/Pt input: ±0.1% of PV
• Analog input: ±0.1% FS
Universal Sensor Inputs
• Universal thermocouple/Pt/analog
Sampling Period
• 60 ms
(current/voltage) inputs.
Event Inputs
• None
• Two
(48 x 48 mm)
E5CN-H
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 2
• None
• Voltage output
(for driving SSR)
2-level Display: PV and SV
Auxiliary Outputs
• Two
Refer to Operation for E5
operating procedures.
Refer to Safety Precautions for E5
5-digit Display with high resolution of 0.01°C
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Logic operations
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485 or
RS-232C communications
@
48 × 48 mm
E5CN-H
N/ E5
CSM_E5CN-H_DS_E_4_1
@
N-H for
@
N/E5
@
N-H.
1

Related parts for E5CN-HQ2M-500 AC100-240

E5CN-HQ2M-500 AC100-240 Summary of contents

Page 1

... This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159) ...

Page 2

... Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). 1 control output Fully universal input 2 control outputs Option Units E53-@@@@ Applicable Controller CN: E5CN-H or E5CN 2. Function 1 Blank: None Q: Control output 2 (voltage output for driving SSR) P: Power supply for sensor C: Current output 3. Function 2 Blank: None ...

Page 3

... DIN 48 × 48 × × H × D) 100 to 240 VAC Silver 24 VAC/VDC Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Communications 3-phase heater burnout/SSR failure/ RS-485 Heater overcurrent detection Heater burnout/SSR failure/ Heater overcurrent detection ...

Page 4

... Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) Power consumption 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) Any of the following can be selected (i.e., fully universal input). Thermocouple Sensor input ...

Page 5

... JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) E5CN-H Analog input 2300.0 1800.0 1700.01700.0 1300.0 1300.0 Usable in the following ranges by scaling: − ...

Page 6

... Controllers User's Manual Basic Type (Cat. No. H156) for H < > 0 information on the loop burnout alarm (LBA). ⏐H⏐ ≥ ⏐L⏐ *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature H > < 0 Controllers User's Manual Basic Type (Cat. No. H156) for ⏐H⏐ ≤ ⏐L⏐ information on the PV change rate alarm ...

Page 7

... Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H. Setup Tool port An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. *4 Approved UL 61010-1, CSA C22.2 No. 1010-1 ...

Page 8

... ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 E5CN-H 250 VAC, 30 VDC 3 (resistive load) cosφ Switching current (A) E5CN ...

Page 9

... B (+) 11 RS-485 12 A (−) DO NOT 13 USE CT2 14 CT1 15 E5CN-H Auxiliary outputs Auxiliary outputs (relay outputs) (relay outputs) 250 VAC (resistive load) Auxiliary output 2 A heater burnout alarm, SSR failure, heater overcurrent alarm, Auxiliary output 1 or input alarm is sent to the ? output to which the alarm 1 function is assigned ...

Page 10

... Mounting Adapter Terminal Cover (Accessory) (E53-COV17) (Accessory) Note: The terminal block cannot be removed. (2,100) LED indicator 250 (SD) E5CN-H No. 1 display No. 2 display Up Key (Unit: mm) Panel Cutout Group Mounted +1.0 (48 × number of units − 2.5) Group mounting does not allow waterproofing. ...

Page 11

... Two, 3.5 dia. 2.36 dia. 12 dia. 9 Two, M3 (depth: 4) Armature Lead E5CN-H E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Maximum continuous heater current (50/60 Hz) Number of windings: 400±2 Winding resistance: 18±2 Ω 100 ∞ 10 Distortion 1 kΩ ...

Page 12

... Adapter Y92F-45 Note: 1. Use this Adapter when the panel has already been prepared for the E5B@. 2. The Adapter is available only in black. Mounted to E5CN-H 4.7 76 69.6 to 77.6 72 × 72 Panel ( mm) 72 × × 48 2.2 4.7 77.3 (to back of E5CN-H) E5CN-H Fixture (Accessory) 67 × ...

Page 13

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...

Related keywords