C200HW-PA204C Omron, C200HW-PA204C Datasheet - Page 6

no-image

C200HW-PA204C

Manufacturer Part Number
C200HW-PA204C
Description
Power Supply
Manufacturer
Omron
Datasheet

Specifications of C200HW-PA204C

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
6
General Specifications
Note: The Power Supply Unit must be stored at an ambient temperature of –25 to 30°C and a humidity of 25% to 70% to maintain the maintenance forecast monitor
Item
Power supply voltage
Allowable voltage range
Power consumption
Inrush current
Power supply capacity
Power supply output terminals
(service power supply)
RUN output
Monitor display
Maintenance forecast
monitor output
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient operating temperature
Ambient operating humidity
(See note.)
Atmosphere
Ambient storage temperature
(See note.)
Grounding
Enclosure
Weight
Dimensions
Safety standards
function when the Unit is stored without power supplied for more than three months.
Model
100 to 240 V AC (wide-range), 50 to 60 Hz
85 to 264 V AC, 47 to 63 Hz
100 VA max.
100 to 120 V AC input: 15 A max. (for a cold start at room temperature)
200 to 240 V AC input: 30 A max. (for a cold start at room temperature)
4.6 A at 5 V DC, 0.625 A at 26 V DC, 30 W total
None
None
7-segment display
Yes (open-collector output)
50 mA max. at 30 V DC max.
20 MΩ min. (at 500 V DC) between AC external and GR terminals as well as between all output terminals
20 MΩ min. (at 250 V DC) between all output and GR terminals
2,300 V AC at 50/60 Hz for 1 min between AC external and GR terminals as well as between all output terminals,
Leakage current: 10 mA max.
1,000 V AC at 50/60 Hz for 1 min between all output and GR terminals, Leakage current: 10 mA max.
2 kV on power supply line (conforming to IEC61000-4-4)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, Acceleration: 9.8 m/s
80 minutes (Sweep time 8 min x 10 = total time 80 min.) (according to JIS C0040)
Acceleration: 147 m/s
0 to 55°C
0% to 90% (with no condensation)
Must be free from corrosive gases.
–20 to 75°C
Less than 100 Ω
Mounted in a panel.
500 g max.
54 x 130 x 111 mm (W x H x D)
(including the maintenance forecast monitor display module)
Conforms to cULus and EC Directives .
N and Lloyd (approval pending)
2
, 3 times each in X, Y, and Z directions (according to JIS C0040)
C200HW-PA204C
2
100 VA max.
5 A at 5 V DC, 0.8 A at 24 V DC, 25 W total
400 g max.
80 x 90 x 81.6 mm (W x H x D)
in X, Y, and Z directions for
CJ1W-PA205C