E53-COV07 Omron, E53-COV07 Datasheet

no-image

E53-COV07

Manufacturer Part Number
E53-COV07
Description
TERMINAL COVER E5CK
Manufacturer
Omron
Datasheets

Specifications of E53-COV07

Accessory Type
Terminal Cover
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
E5CK
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E53COV07
1
Ordering Information
Advanced Process Digital
Controllers with Fuzzy Logic
D
D
D
D
D
D
D
D
D
D
D
D
Note: Order Control Output Boards and Option Boards separately below.
Note: 1. When using the heater burnout alarm function with a standard model, the Linear Output Module cannot be used for the control
Standard model
Position-proportional model (See Note 3)
Standard model
Position-proportional model (See Note 3)
Standard model
Non-standard model with built-in quick auto-tune button
(See Nomenclature section for details)
Field configurable outputs, options.
100 ms sampling (for analog input).
Advanced PID, or fuzzy self-tuning.
Conforms to UL, CSA and CE standards.
Water-resistant front panel meets IP66/NEMA 4X.
Remote set point with optional event input board.
Set point ramp.
Serial communications available.
Front panel programming.
Heat only or heat/cool control.
Auxiliary outputs (SPST) standard; two for E5AK/E5EK,
one for E5CK.
3-year warranty.
E5 K
Digital Process Controller Series
2. E5EK-PRR2/E5AK-PRR2 controllers are supplied with dedicated relay output.
3. Position-proportional models are intended for motorized valves (not 4-20 mA modulating valves). These use two relays (“open”
4. Part numbers ending in --500 include a Finger Safe cover.
Digital Process Controller
outputs (heat). The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at
4 to 20 mA for the current outputs.
and “close”) which will turn a motor clockwise or counter-clockwise, thus opening or closing the valve.
Description
E5 K
1/4 DIN
(96
(96 x 96 mm)
1/8 DIN
(48
(48 x 96 mm)
1/16 DIN
(48
(48 x 48 mm)
/
/
/
DIN size
96
96
48
)
)
)
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
100 to 240 VAC
Supply voltage
E5AK-AA2-500
E5AK-PRR2-500
E5EK-AA2-500
E5EK-PRR2-500
E5CK-AA1-500
E5CK-AA1-302
Model

Related parts for E53-COV07

E53-COV07 Summary of contents

Page 1

Digital Process Controller Series E5 K Advanced Process Digital Controllers with Fuzzy Logic Field configurable outputs, options. D 100 ms sampling (for analog input). D Advanced PID, or fuzzy self-tuning. D Conforms to UL, CSA and CE standards. D Water-resistant ...

Page 2

... E5AK 1 E5CK 1 E5EK 1 All Model E53-R E53-S E53-Q E53-Q3 E53-Q4 E53-C3 E53-C3D E53-V34 E53-V35 E53-R4R4 E53-Q4R4 E53-Q4HR4 E53-C4R4 E53-C4DR4 E53-V44R4 E53-Q4Q4 E53-Q4HQ4H E53-AK01 E53-CK01 E53-AK02 E53-AK03 E53-CK03 E53-AKB E53-CKB E53-AKF E53-CKF Model E54-CT1 E54-CT3 E53-COV0809 E53-COV07 E53-COV08 Thermo Tools (See Note) ...

Page 3

Input Types (selectable with input jumper connector) Thermocouple Input (field selectable) (See Notes) Range --200 0.0 --100 0.0 ° 1,300 500.0 850 400.0 --300 0.0 --100 0.0 ° 2,300 ...

Page 4

... Approximately 2600 steps (Input impedance: 150 Ω) Connect only an Omron Current Transformer (E54-CT1 or E54-CT3) Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter, MV change rate limiter, input digital filter, input shift, run/stop, protect functions ...

Page 5

J Characteristics Indication accuracy (See Note) Hysteresis Proportional band (P) Integral (reset) time (I) Derivative (rate) time (D) Control period Manual reset value Alarm setting range Sampling period Temperature input Analog input Insulation resistance Dielectric strength Vibration resistance Malfunction Mechanical ...

Page 6

J Option Board Ratings and Characteristics Event inputs Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. No-contact input: ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max. Communications Interface RS-232C and RS-485; RS-422 for E5AK ...

Page 7

Nomenclature J E5AK Operation Indicators A/M Key Display Key J E5EK Operation Indicators Display Key A/M Key J E5CK Operation Indicators A/M Key Display Key J E5CK-302 Operation Indicators AT Key Display Key Operation Indicators • OUT1 No. 1 display ...

Page 8

... Controller. This mode will be accessible only when an option board is installed in the controller. Calibration Mode For calibrating inputs and transfer output. Calibrate the selected input type. Transfer output can be calibrated only when the Communications Unit (E53-CKF) has been installed in the Controller. 8 ...

Page 9

Dimensions Unit: mm (inch) J E5AK 96 (3.78 (3.78) Note: 1. Recommended panel thickness mm. J E5EK 48 (1.89) J E5CK Panel Cutouts 65 min. 60 min 13.5 ...

Page 10

... The E5CK-302 model has the same dimension and cutouts as the E5CK. J Accessories (Order Separately) Terminal Cover for E5AK E53-COV0809 43.2 (1.70) Terminal Cover for E5CK E53-COV07 44.3 (1.74) 44.3 (1.74) Current Transformer (E5AK and E5EK only for Heater Burnout Alarm) E54-CT1 21 (0 ...

Page 11

Installation J Remove Controller From Rear Housing E5AK and E5EK To pull out the internal mechanism from the housing, use a Phillips screwdriver matching the screw on the lower part of the front panel. 1. Turn the screw counterclockwise while ...

Page 12

J Settings Note: Always turn off the power supply to the Digital Controller before changing any switch settings standard model, set up the Output Modules for control outputs 1 and 2 before mounting the Controller position-proportional ...

Page 13

E5EK 1. Remove the Power Board in the order shown in the following diagram. Power board E5CK 1. Two rectangular holes are provided on the Power Board (right side of Controller). Fit the two protrusions of the output board into ...

Page 14

J Mounting Controller E5AK and E5EK 1. Insert the controller into the panel’s mounting hole at the position shown in the figure below. 2. Fit the mounting bracket (accessory) into the mounting slots on the top and bottom of the ...

Page 15

... Potentiometer RSP: Remote SP input E5CK 1. The E5CK-AA1-500 Controller is provided with a Terminal Cover (E53-COV07). Fasten the Terminal Cover as fol- lows by using the plastic pin. Wiring In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller. Power Supply ...

Page 16

Wiring Terminals for E5EK E5EK Terminal Arrangement AC100--240V~ 50/60 Hz OPTION SENSOR INPUT TRSF: Transfer output EV1/2: Event input PTMR: Potentiometer RSP: Remote SP input J Wiring Terminals for E5CK E5CK Terminal Arrangement OUT1 100--240VAC ...

Page 17

J Input Wiring E5AK Connect the sensor input to terminal numbers and 33 as follows according to the input type. E5EK Connect the sensor input to terminal numbers and 23 as follows according to ...

Page 18

... E5AK-PRR2/E5EK-PRR2 Controllers The E5AK-PRR2 and E5EK-PRR2 Controllers are supplied with relay output. This relay output is not compatible with any other module. When replacing the Output Module, use the E53-R. The following diagrams show the relationship between terminals and open/close relay settings. ...

Page 19

... E53-Q4HR4 E53-Q4Q4 E53-Q4HQ4H + + Relay NPN E53-R4R4 /E53-V44R4 E53-Q4Q4 E53-Q4R4 /E53-C4R4 E53-Q4HR4/E53-C4DR4 E5EK Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The following diagrams show the internal equalizing circuits for the auxiliary outputs ...

Page 20

J CT Input/Potentiometer (for E5AK and E5EK only) E5AK CT Input/Potentiometer When using the HBA function on the E5AK-AA2 Controller, connect Current Transformer input (CT) to terminal numbers 15 to 17. When monitoring the valve opening on the E5AK-PRR2 Controller, ...

Page 21

... Part number Use event inputs under the following conditions: Contact input No-contact input Communications Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with Communications Units (E53-AK01/02/03). For details on wir- ing, refer to Chapter 6, Using the Communications Function in your User’s Manual ...

Page 22

... Contact input No-contact input Communications Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with Communications Units (E53-AK01/02/03). For details on wiring, refer to Chapter 6, Using the Communications Function in your User’s Manual. E5CK Terminal numbers 1, 13, and 14 are valid only when the Option Board is set in the Controller The following four connections are possible depending on the model of the Option Board ...

Page 23

J Connection Example of Digital Controller And SSR Digital Controller + Voltage output terminal (for driv- ing SSR) -- Connectable E5AK/E5EK Digital Controller with Voltage Output (12 VDC max.) E5CK Digital Controller with Voltage Output (12 VDC, 20 ...

Page 24

Precautions J Precautions when Wiring Use wire ducts to separate input leads and power lines in • order to protect the Controller and its lines from external noise. Solderless terminals are recommended when wiring the Con- • troller. Power Blocks ...

Page 25

J Operation • For models with alarm functions: The alarm outputs of a mod- el with an alarm function may not turn ON properly when the model malfunctions. The use of alarm equipment with the model is recommended. • The ...

Page 26

... Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority ...

Page 27

... OMRON ELECTRONICS LLC • THE AMERICAS HEADQUARTERS Schaumburg, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com OMRON CANADA, INC. • HEAD OFFICE Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron.ca OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON ELECTRONICS MEXICO • ...