YD630M ETERNA, YD630M Datasheet

EMERGENCY LIGHT, MAINTAINED, 8W

YD630M

Manufacturer Part Number
YD630M
Description
EMERGENCY LIGHT, MAINTAINED, 8W
Manufacturer
ETERNA
Datasheet

Specifications of YD630M

Length
345mm
Width
120mm
Depth
75mm
Ip/nema Rating
IP65
Svhc
No SVHC (15-Dec-2010)
Base Type
300mm T5 Fluorescent
External Depth
75mm
External Length / Height
345mm
External Width
120mm
Lamp Base Type
300mm T5 Fluorescent
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Cleaning:
>
Lamp replacement:
>
>
>
>
>
>
Replacement lamp type:
Wattage:
Type:
Replacement battery type:
2.4V Ni-Cad 2 x D cells
7030-0621
Eventually, you may want to replace this light fitting:
When your light fitting and or battery pack come to the end of their life or you choose to update or
upgrade the fitting by replacing it, please do not dispose of it with your normal household waste, please
recycle where facilities exist. When you need to dispose of this fitting, check with your retailer or local
authority for suitable options. New regulations will encourage the recycling of Waste from Electrical and
Electronic Equipment ( European “WEEE Directive” effective August 2005 ).
If you experience problems:
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our Helpline
for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not be able to
give specific instructions regarding individual installations.
If in doubt, consult a qualified electrician.
Help line:
Tel: 01933 673 144
For answers to frequently asked questions ( FAQs ) and other information visit our web-site
www.eterna-lighting.co.uk
Clean this light fitting only with a soft dry cloth—Do
not use any chemical or abrasive cleaners.
Switch off the electricity at the mains.
Remove the diffuser.
Twist and withdraw the tube.
Insert new tube.
Restore the power and perform operation check.
Replace diffuser.
8 W
T5 fluorescent tube
Fax: 01933 678 083
Email: sales@eterna-lighting.co.uk
Battery replacement:
If after routine operation check, the lamp does not
remain lit for the three hour period, a new battery pack
may be required.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10) Plug battery pack into circuit board.
11) Close and secure gear tray
12) Replace diffuser.
13) Restore power and allow to charge for 24 hours.
14) Perform full operation check and update test record.
Switch off the electricity at the mains.
Allow batteries to fully discharge then reconnect to
supply and allow to charge for 24 hours.
Test again for 3 hours, if light does not remain lit
change the battery pack as follows:
Remove the diffuser.
Remove the two screws indicated on the gear tray
and open the fitting.
Unplug the battery lead from the circuit board.
Remove the two screws in the top of the gear tray
beneath the lamp that secure the battery pack in
place and lift the battery pack out of the fitting.
Write current date on the new battery pack.
Fit new battery pack securing in place using the
screws removed from the old pack.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING
Specification:
Power
Continuous illumination
Battery
Recharge time
Over-discharge protection
Maintained emergency bulkhead
convertible to non-maintained by removing link
PLEASE RETAIN FOR FUTURE REFERENCE
YOUR NEW FITTING
light 8W
>3 hours @ 45Lm
YD630M
2.4V 4.5Ah
Model(s)
~20 hours
- -
Yes
8W
BLF
EBLF
30.2%
17.7%

Related parts for YD630M

YD630M Summary of contents

Page 1

... Fax: 01933 678 083 Email: sales@eterna-lighting.co.uk For answers to frequently asked questions ( FAQs ) and other information visit our web-site www.eterna-lighting.co.uk Maintained emergency bulkhead light 8W convertible to non-maintained by removing link Model(s) YD630M Specification: Power 8W Continuous illumination >3 hours @ 45Lm Battery 2.4V 4.5Ah Recharge time ...

Page 2

... During this period all fittings should be examined visually to ensure that they are functioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure that the normal supply has been restored. The duration of the simulated failure shall be:- Each month: Isolate the power supply and check the light is illuminated ...

Related keywords