H5BR-B-AC100-240 Omron, H5BR-B-AC100-240 Datasheet - Page 12

no-image

H5BR-B-AC100-240

Manufacturer Part Number
H5BR-B-AC100-240
Description
TIMER DIGITAL LCD
Manufacturer
Omron
Series
H5BRr
Datasheet

Specifications of H5BR-B-AC100-240

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC
Mounting Type
Panel Mount
Termination Style
Screw Terminal
Timing Adjustment Method
Up/Down Digit Keys
Timing Initiate Method
Input Voltage
Lead Free Status / Rohs Status
Supplier Unconfirmed
Precautions
H5BR
3. To change the selected item,
• The capacity of the external power supply is 80 mA at 12
• If power is interrupted for less than 10 ms, operation will
• Connect the power supply voltage through a relay or switch
• Depending on switching frequency, current surges may
continue normally. If power is interrupted for 10 to 500 ms,
operation will be inconsistent, and timing may stop or reset,
depending on the mode.
in such a way that the voltage reaches a fixed value
immediately.
degrade relay contacts; relays with a capacity greater than
10 A are recommended.
• Press the MODE key until the desired item appears.
VDC. When using a 24 VAC/12 to 24 VDC power supply,
reduce the load with the power supply voltage, as shown in
the following diagram (DC power supplies only).
EXTERNAL POWER SUPPLY
POWER SUPPLIES
12
• Be sure that the capacity of the external power supply is
• Do not use external sources to increase the voltage of input
• Be sure that the load of the control output (contact, transistor)
• The transistor output is opto-isolated from the internal
• The following displays will appear if an error occurs. The
adequate, because the power supply may not provide a
surge current sufficient to start the timer due to the switching
regulator contained in the timer's internal circuitry.
signals (control signal, reset, gate, and key protection).
is less than the maximum values indicated in the
specifications. If the output load exceeds the recommended
value, the life span of the contact output type will be
shortened dramatically, and the transistor of the transistor
output type will be damaged.
circuitry, so either NPN or PNP transistors can be used.
• Change the item setting by pressing keys 1 through 4.
present value and output enter the same status as after
pressing the RESET key.
Display
INPUT AND OUTPUT
SELF-DIAGNOSTIC FUNCTION
(Press the DISPLAY key to switch back from set mode to
run mode.)
Error
CPU
Memory
Output
status
OFF
Correction
Press
RESET
key
(batch
count to 0)
Set
No
change
Set at the
factory
H5BR

Related parts for H5BR-B-AC100-240