60212 SQUARE D, 60212 Datasheet - Page 8

CIRCUIT BREAKER, THERMAL MAG, 1P, 15A

60212

Manufacturer Part Number
60212
Description
CIRCUIT BREAKER, THERMAL MAG, 1P, 15A
Manufacturer
SQUARE D
Series
C60Nr
Datasheet

Specifications of 60212

Actuator Style
Toggle
No. Of Poles
1
Current Rating
15A
Voltage Rating Vdc
60V
Voltage Rating Vac
120V
Mounting Type
DIN Rail
Tripping Characteristic
C
Voltage Ac
120V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Multi 9
UL 489A for DC Telecom Applications
Selection Table
Ratings as per UL489A and IEC 947-2 Standards
Trip Units
Dimensions and Weights
8
Number of Poles
Rated Current (A) at 25°C
Interrupting Ratings
as per UL489A
(kA RMS)
Ultimate Breaking
Capacity (Icu) as per
IEC 947-2 (kA RMS)
Service Breaking Capacity (Ics)
Magnetic Setting
Dimensions H x W x D (in./mm)
Weight (oz/g)
Listed Miniature Circuit Breakers
UL489A C60 Circuit Breakers for use in Communications Equipment (60 Vdc)
C Curve—Magnetic Setting Between 7 and 10 Times Ampere Rating
Ratings and interrupting ratings: page
Cable range: pressure terminals are suitable for copper cables:
c 0.5 to 25 A: #14 to #4 AWG
c 32 to 63 A: #14 to #2 AWG
Width: 1P: 18mm
Rating (A)
10
13
15
20
30
40
50
63
0.5
1
2
3
4
5
6
8
AC 50/60 Hz
DC
AC 50/60 Hz
(% Icu)
DE2
14
240 V
277 V
480Y 277 V
60 V
125 V
240 V
415 V
440 V
C curve
1P
60406
60407
60408
60409
60410
60411
60412
60413
60414
60415
60416
60417
60418
60419
60420
60421
Discount
Schedule
C60
1
0.5–63
10
10
75%
Between 7 and 14 times ampere rating
3.19 x 0.71 x 3.00/81 x 18 x 76
3.85/110
List Price
Additional information:
c Catalog no. 0860CT9501R2/01
80
67
67
67
67
67
67
67
67
67
67
67
67
74
78
82

Related parts for 60212