Specifications of ZUP/NC402

Connector Type
D-Sub 09 pos Male to RS485 8 pos Male
Length
3.28' (1.00m)
Cable Type
Round
Color
White
Shielding
Shielded
Usage
Communication
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
285-1667
5.5.2 ID control commands
5.5.1 Initialization control
4
3
#
1
2
#
1
2
:ADRn;
:RMT?;
Commands
Commands
:RMTn;
:MDL?;
:REV?;
:DCL;
Returns the remote/local setting. The returned data is an ASCII string.
RM1 (The unit is in remote mode)
RM2 (The unit is in latched remote mode)
Sets the power supply address. ADR is followed by the address
which can be 01 to 31.
Sets the power supply to local or remote mode. (This command is active
when the unit is either in Local or Remote modes).Transition from Local to
Remote mode is made via the front panel only.
:RMT0; Transition from Remote to Local mode.
:RMT1; Transition from latched Remote to non-latched Remote.
:RMT2; Latched remote: Transition back to Local mode or to non- latched
Remote can be made via the serial port (RS232/485).
At this mode, the front panel Local/Rem function is disabled. Escape from
this mode to non -latched remote mode can be made by turning the AC
ON/OFF to OFF and after approx. 10sec.to ON again.
Returns the power supply model identification as an ASCII string:
Nemic-Lambda ZUP(XXV)-(YYA).
XX - The rated output voltage
YY - The rated output current
example: Nemic-Lambda ZUP(6V-33A)
Returns the software version as an ASCII string:
Ver XX-YYA.B
XX- The rated output voltage
YY- The rated output current
A.B- Version identifier
example: Ver 6-33 1.0
Clears the communication buffer and the following registers:
1. Operational status register
2. Alarm (fault) status register
3. Programming error register
Description
Description