SU8000RT3U1TF Tripp Lite, SU8000RT3U1TF Datasheet - Page 6

8000VA UPS System SmartOnline Rack/Tower PureSine 8kVA Transformer 120V/208V Output Hardwire Detachable Bypass PDU, 1 RS-232, 2 DB9 & SNMP Slot.

SU8000RT3U1TF

Manufacturer Part Number
SU8000RT3U1TF
Description
8000VA UPS System SmartOnline Rack/Tower PureSine 8kVA Transformer 120V/208V Output Hardwire Detachable Bypass PDU, 1 RS-232, 2 DB9 & SNMP Slot.
Manufacturer
Tripp Lite
Datasheet

Specifications of SU8000RT3U1TF

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Operating
Temperature Range
Storage
Temperature Range
Relative Humidity
AC mode BTU / hr.
(full load)
AC economy mode
BTU / hr. (full load)
AC economy mode
efficiency rating
(100% load)
Operating Elevation
(ft)
Audible Noise
COMMUNICATIONS
Communications
interface
Network monitoring
port description
PowerAlert software
Communications
cable
WatchDog
compatibility
LINE / BATTERY TRANSFER
Transfer time
Transfer time
(economy mode)
Low voltage transfer
to battery power
(setpoint)
High voltage transfer
to battery power
(setpoint)
SPECIAL FEATURES
Cold Start (startup in
battery mode during
a power failure)
Economy mode
operation
High availability UPS
features
Green & high
efficiency features
CERTIFICATIONS
UPS Certifications
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
2732
1020
96%
0-3000m (0 to 10,000 ft.)
60 dBA at front side 1 meter
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports
Included
USB, DB9 serial and EPO cables included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
No transfer time (0 ms.) in online, double-conversion mode
8 ms. typical power failure response in optional economy mode
100V
300V
Cold-start operation supported
Optional economy mode enables high-efficiency bypass operation with a maximum output voltage variation of
+/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1
millisecond transfer time between modes.
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)

Related parts for SU8000RT3U1TF