SU8000RT3U1TF Tripp Lite, SU8000RT3U1TF Datasheet - Page 3

8000VA UPS System SmartOnline Rack/Tower PureSine 8kVA Transformer 120V/208V Output Hardwire Detachable Bypass PDU, 1 RS-232, 2 DB9 & SNMP Slot.

SU8000RT3U1TF

Manufacturer Part Number
SU8000RT3U1TF
Description
8000VA UPS System SmartOnline Rack/Tower PureSine 8kVA Transformer 120V/208V Output Hardwire Detachable Bypass PDU, 1 RS-232, 2 DB9 & SNMP Slot.
Manufacturer
Tripp Lite
Datasheet

Specifications of SU8000RT3U1TF

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Output voltage
regulation (line
mode)
Output voltage
regulation (Economy
line mode)
Output voltage
regulation (Battery
mode)
Built-in UPS output
receptacles
Output circuit
breaker
Output AC waveform
(AC mode)
Output AC waveform
(battery mode)
INPUT
Rated input current
(at maximum load)
Nominal Input
Voltage(s) Supported
UPS input
connection type
UPS input
connection
description
Recommended
Electrical Service
BATTERY
Full load runtime
(minutes)
Half load runtime
(minutes)
Expandable battery
runtime
External battery
pack compatibility
DC system voltage
(VDC)
Battery recharge
rate (included
batteries)
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage
correction
+/- 2%
+/- 10%
+/- 2%
12 5-15/20R outlet(s); 4 L6-20R outlet(s); 2 L6-30R outlet(s)
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each, 20A
single-pole (x4) protect 3 5-15/20R outlets each
Pure Sine wave
Pure Sine wave
44.2A (208V)
208V AC
Hardwire
3 wire single phase input (L1, L2, G)
208V 50A
5.5 min. (7200w)
13.5 min. (3600w)
Supports extended runtime with optional external battery packs
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;
240
Less than 6 hours from 10% to 90%
Hot-swappable, user replaceable external battery packs
2% output voltage regulation in standard online, double-conversion mode
Corrects overvoltages up to 300V
BP240V1407C-1PH

Related parts for SU8000RT3U1TF