MINI-SYS-PS-100-240AC/24DC/1.5 Phoenix Contact, MINI-SYS-PS-100-240AC/24DC/1.5 Datasheet - Page 9

no-image

MINI-SYS-PS-100-240AC/24DC/1.5

Manufacturer Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Description
POWER SUPPLY PRIMARY SWITCH MODE
Manufacturer
Phoenix Contact

Specifications of MINI-SYS-PS-100-240AC/24DC/1.5

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
65Hz
Output Voltage
24VDC
Output Current
1.5A
Input Voltage
85V To 265V
Supply Voltage
RoHS Compliant
No. Of Outputs
1
Supply Voltage Typ
110V AC /
Rohs Compliant
Yes
102050_01_en
Output
They are connected using the "24 V" and "0 V" screw connections on the screw connection of the DC output and via the
DIN rail connector.
Protection of the secondary side
The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is
limited to 30 V DC.
Signaling
For function monitoring, there is the floating DC OK switching output and the DC OK LED.
DC OK LED
Floating DC OK output
Meaning
max.
30 V AC/DC, 1 A
Output 24 V DC
DC OK
2
State 1
Closed
Normal operation of the power supply
(U
ON
OUT
> 21.5 V)
Floating contact
The floating signal contact opens and signalizes a drop in the
output voltage of 21.5 V. Signals and ohmic loads of up to
30 V and currents of up to 1 A can be connected. For heavily
inductive loads such as a relay, a suitable protection circuit
(e.g. damping diode) is necessary.
Make sure that all output lines are dimen-
sioned according to the maximum output cur-
rent or are separately protected. The cables on
the secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
MINI-SYS-PS-100-240AC/24DC/1.5
State 2
OFF
Open
1. The output voltage is less than
21.5 V. There is a secondary consumer
short circuit or overload.
2. There is no input voltage or there is a
device fault.
PHOENIX CONTACT