MINI-SYS-PS-100-240AC/24DC/1.5 Phoenix Contact, MINI-SYS-PS-100-240AC/24DC/1.5 Datasheet - Page 10

no-image

MINI-SYS-PS-100-240AC/24DC/1.5

Manufacturer Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Description
POWER SUPPLY PRIMARY SWITCH MODE
Manufacturer
Phoenix Contact

Specifications of MINI-SYS-PS-100-240AC/24DC/1.5

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
65Hz
Output Voltage
24VDC
Output Current
1.5A
Input Voltage
85V To 265V
Supply Voltage
RoHS Compliant
No. Of Outputs
1
Supply Voltage Typ
110V AC /
Rohs Compliant
Yes
102050_01_en
Function
U
[V]
OUT
U
N
I
I
BOOST
N
0
0
< 60 °C
Ambient temperature [°C]
20
I
N
< 40 °C
40
I
BOOST
60
I
[A]
OUT
Output characteristic curve
The device can supply a nominal output current of 1.5 A with
ambient temperatures of up to 60°C. At an ambient temper-
ature of up to 40°C, the device supplies a continuous output
current of 2 A. At temperatures up to 60°C, the POWER
BOOST provides a transient output current of 2 A for a few
minutes. In the event of a higher load, the operating point fol-
lows the U/I characteristic curve depicted in the figure.
In the case of overload or short-circuit, the full output current
I
the device does not switch off. As soon as the overload or
short-circuit is no longer present, the full secondary voltage
is once again available.
The U/I characteristic curve ensures that both heavily capac-
itive loads and devices with DC/DC converters in the primary
circuit can be fed without problems using MINI POWER.
Downstream fuses are triggered reliably. Selectivity in the
design of your system is guaranteed at all times.
U
I
I
Thermal behavior
With an ambient temperature of up to +60°C, the device sup-
plies the continuous output current of I
ent temperatures above +60°C, the output current must be
reduced by 2.5% per Kelvin increase in temperature. The de-
vice does not switch off at ambient temperatures of +70°C or
thermal overload. The output capacity is reduced as far as
necessary to provide device protection. After it has cooled
down, the output capacity is increased again.
BOOST
N
BOOST
N
= 1.5 A
= 24 V
is supplied permanently with reduced output voltage,
= 2 A
MINI-SYS-PS-100-240AC/24DC/1.5
N
PHOENIX CONTACT
. In the case of ambi-
10