ADN10-24-1PM Emerson Network Power, ADN10-24-1PM Datasheet

PSU, DIN RAIL, 24V, 10A

ADN10-24-1PM

Manufacturer Part Number
ADN10-24-1PM
Description
PSU, DIN RAIL, 24V, 10A
Manufacturer
Emerson Network Power
Datasheet

Specifications of ADN10-24-1PM

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Output Voltage
24V
Output Current
10A
Power Rating
240W
Input Voltage
115VAC / 230VAC
Supply Voltage Typ
115VAC /
No. Of Outputs
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
190
60-480 Watts
ADN Series
Storage/Shipment
Operating (convection)
Humidity
Power Factor Correction
Auto Select 115/230 VAC, 50/60 Hz Input
All Single Phase models meet SEMI F47
Sag Immunity
Class 1, Div 2 Hazardous Locations
DC OK Signal
Adjusable Voltage
Industrial grade design (no derating to 60°C)
User-friendly front panel
Single and three phase inputs available
Highly efficent >90% switching technology
High MTBF and reliability
Peak current capability 2x rated current
for 2 seconds
Three year warranty
NEC Class 2 on models <100W
Americas: (760) 930-4600
Special Features
Environmental
-10° C to +60° C (derate
to 50% at +70° C)
<90% RH noncondensing per
IEC 68-2-2, 68-2-3
IP20 (EN60529), protection
from moisture & condensation
-25°C to +85°C
Technical Support: (888) 41ASTEC or (407) 241-2752
Europe (UK) 44 (1384) 842-211
Total Power:
Input Voltage:
# of Outputs:
Input
Nominal voltage
Power factor (PFC)
AC Input range
DC Input range
Frequency
Output
Nominal voltage
Holdup time
Tolerance
Tolerance
Line regulation
Load regulation
Time & temp. drift
Initial voltage setting
Ripple
Power back immunity
Parallel Operation
Over voltage protection
EMC
Emissions
Immunity
Approvals
Protection
ADN20-24-1PM
All others
60 - 480 Watts
115/230 VAC
One
Electrical Specs
EN 61000-6-3, Class B EN55011, EN55022 Radiated
Conducted including Annex A
Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4
input and level 3 output. EN61000-4-5 Isolation class
4, EN61000-4-11, Transient protection according to
VDE 0160/W2 over entire load range.
EN60950, UL508 Listed, cULus, UL 60950, cURus, CE
(LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC).
EN61000-3-2, EN60079-15 (Class 1, Division 2
hazardous location, Groups A, B, C, D w/ T3 temp
class up to 60°C Ambient.) SEMIF47 Sag Immunity.
For models <100W, UL60950 testing to include
approval as NEC Class 2 power supply acc. To NFPA 70
art. 725-41 (a)(2).
Class 1 (IEC536), degree of protection
SELV rated per EN60950
EN 61000-6-2, EN61000-4-2 Level 4, EN61000-4-3
Asia (HK) 852-2437-9662
Safety
115/230 VAC auto select
EN61000-3-2
85-123 / 176-264VAC
210-375VDC
47-63 Hz, 500 Hz
24V (22.5-28.5VDC Adj.)
> 20ms at full load (25°C)
< ±2 % overall
(combination line/load/time/temp)
< ±2 % overall
<0.5%
<0.5%
24.5V ± 1%
< 50mVpp
> 35V
Switch selectable
Jumper selectable via front panel
< 33VDC
<1%
rev 09.08.05