PAXDR000 Red Lion Controls, PAXDR000 Datasheet - Page 6

no-image

PAXDR000

Manufacturer Part Number
PAXDR000
Description
AC, Dual Rate, Upgradeable Red
Manufacturer
Red Lion Controls
Type
Rate/Totalizerr
Datasheet

Specifications of PAXDR000

Accuracy
± (0.01% of Input Signal Frequency)
Cut Out, Panel
3.62W x 1.77H Inches
Dimensions
3.80W x 1.95H Inches
Display Digit Height
.56 Inches
Display Type
LED Adjustable
Function
Rate/Totalizer
Input Type
Switch Selectable Pulse
Keypad Type
3 Programmable Function (5 Keys Total)
Number Of Digits
Rate = 5, Totalizer = 8
Primary Type
Electronic
Range, Measurement
Rate = 0 to 99999, Totalizer = ±99999999
Special Features
Programmable Function Keys
Termination
Cage Clamp
Voltage, Supply
85 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
specific functions. These cards plug into the main circuit board of the meter. The
Plug-in cards have many unique functions when used with the PAX. The
literature that comes with these cards should be discarded, unless it specifically
states in the Plug-in Card literature that the information applies to the PAX.
3.0 I
Finger
The Plug-in cards are separately purchased optional cards that perform
Hold
Connectors
Communications
CAUTION: The Plug-in card and main circuit board contain static
sensitive components. Before handling the cards, discharge static
charges from your body by touching a grounded bare metal
object. Ideally, handle the cards at a static controlled clean
workstation. Also, only handle the cards by the edges. Dirt, oil or
other contaminants that may contact the cards can adversely
affect circuit operation.
NSTALLING
Main
Board
Circuit
Serial
Card
Alignment
Slots
TOP VIEW
P
LUG
Analog Output
Card
Setpoint
Output
Card
-I
Finger
Hold
N
6
C
To Install:
1. With the case open, locate the Plug-in card connector for the card type to be
2. Install the Plug-in card by aligning the card terminals with the slot bay in the
3. Slide the meter base back into the case. Be sure the rear cover latches fully
4. Apply the Plug-in card label to the bottom side of the meter in the designated
Quad Sourcing Open Collector Output Card Supply Select
* If installing the Quad sourcing Plug-in Card (PAXCDS40), set the
jumper for internal or external supply operation before continuing.
ARDS
installed. The types are keyed by position with different main circuit board
connector locations. When installing the card, hold the meter by the rear
terminals and not by the front display board.*
rear cover. Be sure the connector is fully engaged and the tab on the Plug-in
card rests in the alignment slot on the display board.
into the case.
area. Do Not Cover the vents on the top surface of the meter. The surface of
the case must be clean for the label to adhere properly.
External Supply
(30 V
Internal Supply
(24 V)
max
)

Related parts for PAXDR000