CV500-ZS3AT1-EV2 Omron, CV500-ZS3AT1-EV2 Datasheet - Page 65

no-image

CV500-ZS3AT1-EV2

Manufacturer Part Number
CV500-ZS3AT1-EV2
Description
C.V SOFTWARE 3.5in DISK
Manufacturer
Omron
Datasheet

Specifications of CV500-ZS3AT1-EV2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Power Supply Units
Power Requirements
DC Power Supply Units: CV500-PS211
Power Requirements
Internal Fuse
52
!
Caution
Abide by the following precautions when wiring the Power Supply Units. Failure
to abide by these precautions my cause faulty operation or damage to the Unit.
A CV-series PC consumes up to 200 VA per Rack. Power consumption varies
with the system configuration (refer to 3-4-6 Current Consumption ). When pow-
er is applied, a surge current five times the steady-state current will flow to the
PC.
A CV-series PC can consume up to 100 W of power per Rack. Power consump-
tion varies depending on the system configuration (refer to 3-4-6 Current Con -
sumption ). When power is applied, a surge current several times the
steady-state current will flow to the PC.
Do not turn on power to the DV Power Supply Unit while the 5-V output terminals
are closed. If power is supplied when the 5-V output terminals are closed, the
internal fuse may blow.
Be sure that no wire clippings or other foreign materials enter the Units when
wiring.
Provide circuit breakers and other protective devices to protect the system
again external short circuits.
Check and recheck all wiring before supplying power to the system.
After wiring the terminals check the terminal block to be sure it is firmly locked
in place.
Screw (3.5 mm head with
self-raising pressure plate)
+
Power Line
twisted-pair cable
(cross-sectional area: 2
mm
ity.
Use AWG 14
Do not reverse polar-
2
min.)
Breaker
DC power source
within the specified range
(refer to Appendix B Specifi -
cations )
Supply 24 VDC
Keep voltage fluctuations
Section 3-4

Related parts for CV500-ZS3AT1-EV2