CV500-ZS3AT1-EV2 Omron, CV500-ZS3AT1-EV2 Datasheet - Page 62

no-image

CV500-ZS3AT1-EV2

Manufacturer Part Number
CV500-ZS3AT1-EV2
Description
C.V SOFTWARE 3.5in DISK
Manufacturer
Omron
Datasheet

Specifications of CV500-ZS3AT1-EV2

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Mounting Racks
3-3-1 Duct Work
When mounting the PC in a control panel, mount the Racks to an intermediate
plate. Holes for mounting the Racks to the intermediate plate should be drilled at
intervals shown in the following diagram. Completely ground the intermediate
mounting plates. Use conductor-plated plates to improve noise immunity.
If power cables carrying more than 10 A at 400 V or 20 A at 220 V must be run
parallel to I/O wiring, leave at least 300 mm between the power cables and the
I/O wiring, as shown in the following diagram.
1 = I/O wiring
2 = General control wiring
3 = Power cables
Four, M5
70 to 120
Four, M5
CV500-BC101/BI111/112
CVM1-BC103/BI114
CV500-BC051/BI062
CVM1-BC053/BI064
CV500-BC031/BI042
250
250
Low current cables
Control cables
Power cables
1
2
3
Model
Grounding at resistance
of less than 100
CPU Backplane
CV500-BC101/051/031
CVM1-BC103/053
Expansion CPU Backplane
Expansion I/O Backplane
CV500-BI111/112/062/042
CVM1-BI114/064
300 mm min.
300 mm min.
W
L
480
306
236
W
465
291
221
L 0.5
170 to 220
150 0.5
150 0.5
Section 3-3
49