61F-GP-N AC220 Omron, 61F-GP-N AC220 Datasheet - Page 3

no-image

61F-GP-N AC220

Manufacturer Part Number
61F-GP-N AC220
Description
LEVEL CONTROL
Manufacturer
Omron
Series
61Fr
Type
Level Control - General Purposer
Datasheets

Specifications of 61F-GP-N AC220

Applications
Supply and Drain Control
Mounting Type
Socket Mount (11 pos)
Voltage - Supply
220VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
61F-GP-NAC220
61FGPNAC220
Connections
Automatic Water Supply and Drainage Control
1. Water supply
• Connect electromagnetic switch coil terminal A to Tb.
• The pump stops when the water level reaches E1 and starts when
Operation
The conductive type level controller consists of a plug-in controller
connected to a set of stainless steel probes. These are cut to length
and inserted vertically into the liquid. A low voltage is applied
between these probes and the earth probe (or tank, if it is electrically
conductive). The water provides a current between the earth probe
and the high-level probe. The output relay in the controller is ener-
gized when the water level reaches the high-level probe and de-ener-
gized when the water level falls below it.
Dimensions
Note: Note:All units are in millimeters unless otherwise indicated.
the water level drops below E2.
49.4
38
38
Electromagnetic
switch
220 or
240 VAC
MCCB
70
70
84
80
Power source
Conductive Level Controller
R S T
2. Drainage
• Connect the electromagnetic switch coil terminal A to Ta.
• The pump starts when the water level reaches E1 and stops when
Note: 1. The diagram shows the connections for water supply. When
For two-point control a low-level probe is used as well. In this case
the relay does not de-energize until the water level falls below the
low-level probe. Using the low-level probe allows a wide differential
between switching a pump on and off, and can avoid excessive pump
operation during tank emptying or filling. If this differential is not
required, the low-level probe need not be connected.
the water level drops below E2.
M
2. The earth terminal must be grounded.
A
draining, change the connection Tb to Ta.
P
Reservoir
3
2
Tb
Ta
4
1
E3
Tc
61F-GP-N2
S2
E2
8
5
Stop
Start
61F-
GP-N2
PF083A
E1
S1
6
7
91
E1
E2
E3
Earth
Tank
3