CS1W-CN313 Omron, CS1W-CN313 Datasheet - Page 81

no-image

CS1W-CN313

Manufacturer Part Number
CS1W-CN313
Description
"CABLE CS1 EXP I/O,30cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN313

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Output Unit Specifications
2-3
2-3-1
Name
Max. Switching
Capacity
Min. Switching
Capacity
Relay
Service Life of
Relay
ON Delay
OFF Delay
No. of Outputs
Internal Current
Consumption
Weight
Circuit
Configuration
Terminal
Connections
Item
Output Unit Specifications
Contact Output Units
8-point Contact Output Unit
2 A, 250 V AC (cos = 1)
2 A, 250 V AC (cos = 0.4)
2 A, 24 V DC (16 A/Unit)
10 mA, 5 V DC
G6D-1A
Electrical: 300,000 operations (resistive load)
100,000 operations (inductive load)
Mechanical: 20,000,000 operations
(See note.)
10 ms max.
5 ms max.
8 points (independent commons)
430 mA max. at 5 V DC
200 grams max.
Internal
Circuits
Internal
Circuits
Note The values for relay service life in the above table represent the minimum val-
Output
LED
Output
LED
ues. The following chart gives reference values for the actual service life.
CQM1-OC221
COM0
COM1
COM2
COM3
COM4
COM5
COM6
COM7
OUT0
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
NC
NC
A0
A1
A2
A3
A4
A5
A6
A7
A8
OUT0
COM0
OUT7
COM7
B0
B1
B2
B3
B4
B5
B6
B7
B8
Maximum
250 V AC: 2 A
24 V DC: 2 A
16-point Contact Output Unit
2 A, 250 V AC (cos = 1)
2 A, 250 V AC (cos = 0.4)
2 A, 24 V DC (8 A/Unit)
10 mA, 5 V DC
G6D-1A
Electrical: 300,000 operations (resistive load)
100,000 operations (inductive load)
Mechanical: 20,000,000 operations
(See note.)
10 ms max.
5 ms max.
16 points (16 points/common, 1 circuit))
850 mA max. at 5 V DC
230 grams max.
Internal
Circuits
Output
LED
OUT1
OUT3
OUT5
OUT7
OUT9
OUT11
OUT13
OUT15
OUT10
OUT12
OUT14
CQM1-OC222
COM
COM
OUT0
OUT2
OUT4
OUT6
OUT8
A0
A1
A2
A3
A4
A5
A6
A7
A8
OUT15
OUT0
COM
B0
B1
B2
B3
B4
B5
B6
B7
B8
Maximum
250 V AC: 2 A
24 V DC: 2 A
Section 2-3
59