CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
RUN ERC ERH SYNC X
LED
Y
Z
U
Data Read
Transfer Words
Count Invalid
Data Read CPU
Side Area Type
Invalid
Data Read CPU
Side Start Word
Invalid
Data Read NC Unit
Side Area Type
Invalid
Data Read NC Unit
Side Start Word
Invalid
Data Read Timeout
Data Write
Transfer Words
Count Invalid
Data Write CPU
Side Area Type
Invalid
Data Write CPU
Side Start Word
Invalid
Data Write NC Unit
Side Area Type
Invalid
Data Write NC Unit
Side Start Word
Invalid
Reflected Data
Transfer Error at
Data Write Setup
Error name
The number of transfer words
for data read by a data
transfer bit is outside the
specified range.
The area type on the CPU
side is outside the specified
range for data read by a data
transfer bit.
The setting of the start word
on the CPU side is outside the
specified range for data read
by a data transfer bit.
The setting of the area type on
the PCU side is outside the
specified range for data read
by a data transfer bit.
The setting of the start word
on the PCU side is outside the
specified range for data read
by a data transfer bit.
Data read by a data transfer
bit was not successful.
The number of transfer words
for data write by a data
transfer bit is outside the
specified range.
The setting of the area type on
the CPU side is outside the
specified range for data write
by a data transfer bit.
The setting of the start word
on the CPU side is outside the
specified range for data write
by a data transfer bit.
The setting of the area type on
the PCU side is outside the
specified range for data write
by a data transfer bit.
The setting of the start word
on the PCU side is outside the
specified range for data write
by a data transfer bit.
Data write was executed by a
data transfer bit, in a condition
other than during PCU setup,
to a parameter that becomes
valid at power supply ON,
restart or setup.
Cause
12-3 LED Error Indicator
Check the number of data
transfer words.
Check the setting of the area
type on the CPU side.
Check the setting of the start
word on the CPU side.
Check the setting of the area
type on the PCU side.
Check the setting of the start
word on the PCU side.
Check the operating condition
of the CPU Unit, and then
execute data read again.
Check the number of data
transfer words.
Check the setting of the area
type on the CPU side.
Check the setting of the start
word on the CPU side.
Check the setting of the area
type on the PCU side.
Check the setting of the start
word on the PCU side.
Any data write not during PCU
setup becomes invalid. Check
the area type, starting word
and execution condition for
data write on the PCU.
Remedy
12-26