01230.9-01 STEGO, 01230.9-01 Datasheet - Page 6

Humidity And Temperature Control

01230.9-01

Manufacturer Part Number
01230.9-01
Description
Humidity And Temperature Control
Manufacturer
STEGO
Datasheet

Specifications of 01230.9-01

Mounting Type
DIN Rail
Operating Voltage Max
120V
Operating Temperature Max
60°C
Output Type
Temperature
Supply Voltage
120VAC
Temperature Accuracy ±
1K
Humidity Range
50 To 90% RH
Operating Temperature Min
0°C
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.
STEGO, Inc. · 1395 South Marietta Parkway · Building 800 · Marietta, GA 30067 · Tel: (770) 984-0858 · Fax: (770) 984-0615
01220.0-00
Part No.
1.97” (50 mm)
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
Enclosure heater
Filter fan, cooling equipment, signal device
The MFR 012 electromechanical thermostat is designed to control the relative humidity inside
enclosures. When connected to an enclosure heater (dehumidifier), it will energize the heater
at the humidity set point in order to raise the dew point. This helps prevent damage and mal-
function of electronic components caused by condensation and corrosion.
The MFR 012 can also be used to control cooling fans, warning lights or other devices.
| |
Technical Data
Switching difference
Permissible air velocity
Contact type
Contact resistance
Service life
Min. Switching capacity
Max. Switching capacity
EMC
Connection
Housing
Mounting
Mounting position
Operating temperature
Storage temperature
Dimensions
Weight
Protection type
Approvals
1)
malfunctions of electronic equipment. Long term, this can lead to corrosion and permanent damage of electronic com-
ponents and systems.
Efficient condensation control
Adjustable relative humidity range
High switching capacity
DIN rail mountable
The critical relative humidity level for most components is 65%. Above 65% RH, condensation can form and cause
MFR 012 Mechanical Hygrostat
4% RH (± 3% tolerance) - at 50% RH
50 ft/sec (15m/s)
SPDT / change-over contact
< 10m
> 100,000 cycles
100mA @ AC/DC 20V
5A resistive / 1A inductive @ 250VAC
DC 20W
acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
3-pole terminal, clamping torque 0.5Nm max.:
solid wire - AWG 14 max. (2.5mm²)
stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm²)
plastic, UL 94V-0, light grey
clip for 35mm DIN rail, EN 60 715
vertical
+32 to +140°F (0 to +60°C)
-4 to +176°F (-20 to +80°C)
2.64 x 1.97 x 1.5” (67 x 50 x 38mm)
approx. 2 oz. (60g)
IP20
UL File No. 164102
˜
Setting range
35 to 95% RH
1)

Related parts for 01230.9-01