MPAXR000 Red Lion Controls, MPAXR000 Datasheet - Page 2

Rate Input Module

MPAXR000

Manufacturer Part Number
MPAXR000
Description
Rate Input Module
Manufacturer
Red Lion Controls
Datasheet

Specifications of MPAXR000

Accessory Type
Digital Input Module
Signal Input Type
Count And Rate, Serial Slave
No. Of Digital Inputs
6
For Use With
EPAX 6 Digit Displays
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
6. CERTIFICATIONS AND COMPLIANCES:
7. ENVIRONMENTAL CONDITIONS:
8. MOUNTING REQUIREMENTS:
About the MPAX Input Modules
scaling which allows the EPAX to display most any engineering unit. Once the MPAX is inserted into the EPAX, the unit has the same functions and capabilities of
our PAX Series Intelligent Panel Meters. A full set of PAX programming instructions will be included with the MPAX module.
Selecting Your Display Components and Option Cards
Please use the following chart to identify the appropriate MPAX module and EPAX Display that will satisfy your application.
Adding Option Cards
in cards. The details for each plug-in card can be reviewed in the specification
section of the PAX Bulletin. Only one card from each function type can be
installed at one time. The function types include Setpoint Alarms (PAXCDS),
Communications (PAXCDC), and Analog Output (PAXCDL). The plug-in cards
can be installed initially or at a later date.
SETPOINT ALARMS PLUG-IN CARDS (PAXCDS)
cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:
ANALOG OUTPUT PLUG-IN CARD (PAXCDL)
from the analog output plug-in card. The programmable output low and high
scaling can be based on various display values. Reverse slopes output is possible
by reversing the scaling point positions.
OPTIONAL PLUG-IN CARDS AND ACCESSORIES
Count/Rate/Serial Slave
Count
Rate
Real-Time Clock/Timer
Timer
SAFETY
ELECTROMAGNETIC COMPATIBILITY
Operating Temperature Range: Determined by the MPAX module
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH (non-condensing)
Altitude: Up to 2000 meters
Max. panel thickness is 0.375" (9.5 mm)
Min. panel thickness for NEMA 4/IP65 sealing is 0.060" (1.52 mm)
The MPAX Module serves as the input to the EPAX Display. There are several different modules to cover a variety of inputs. The MPAX module provides input
To build a complete display unit, you will need an EPAX and an MPAX Input Module. The EPAX is only a display and will not operate without an MPAX module.
The PAX and MPAX series meters can be fitted with up to three optional plug-
The PAX and MPAX series has 4 available setpoint alarm output plug-in
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2
No. 1010-1
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
Type 4X Indoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/8843/UL
EMC specifications determined by the MPAX module.
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
PAXCDL10 - Retransmitted Analog Output Card
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
CB Scheme Test Report #04ME11209-20041018
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
SIGNAL TYPE
Issued by Underwriters Laboratories, Inc.
for measurement, control, and laboratory use, Part 1.
WARNING: Disconnect all power to the unit before
installing Plug-in cards.
MPAX MODULES
MPAXCK00
MPAXTM00
MPAXC000
MPAXR000
MPAXI000
85-250 VAC
*
EPAX0600
EPAX0600
EPAX0600
EPAX0600
EPAX0600
DISPLAYS
EPAX
SETPOINT
OPTIONAL PLUG-IN CARD COMPATABILITY
YES
YES
YES
YES
YES
COMMS
YES
YES
YES
-
-
ANALOG
2
YES
-
-
-
-
9. MODULE INSTALLATION:
10. CONNECTIONS: Wiring connections are made to the EPAX terminal
11. CONSTRUCTION: Aluminum front panel, enclosure, and rear cover with
12. WEIGHT: 5 lbs (2.25 kg) (less module)
COMMUNICATION PLUG-IN CARDS (PAXCDC)
series. Only one of these cards can be installed at a time. When programming the
unit via Crimson (for MPAXI000) or SFPAX (for MPAXCK00 or MPAXTM00),
the RS232 or RS485 Cards must be used.
PAXCDC10 - RS485 Serial (Terminal)
PAXCDC20 - RS232 Serial (Terminal)
PAXCDC30 - DeviceNet
PAXCDC40 - Modbus (Terminal)
PAXCDC50 - Profibus-DP
PROGRAMMING SOFTWARE
CRIMSON - MPAXI000 Only
EPAX meter from a PC. Crimson offers standard drop-down menu commands,
that make it easy to program the EPAX meter. The EPAX program can then be
saved in a PC file for future use. A PAX serial plug-in card is required to
program the meter using the software.
SFPAX - MPAXCK00 and MPAXTM00 Only
EPAX meter from a PC. Using the SFPAX makes it easier to program the EPAX
meter and allows saving the PAX program in a PC file for future use. On-line
help is available within the software. A PAX serial plug-in card is required to
program the meter using the software.
24-pin shrouded connector on EPAX engages connector on MPAX module
upon installation. Shroud ensures proper alignment by providing a lead-in for
the module connector.
block and MPAX module via high compression cage-clamp terminal blocks.
MPAX Module Wiring: Instructions are provided in the corresponding PAX
EPAX Terminal Block Wiring:
textured black polyurethane paint for scratch and corrosion resistance
protection. Sealed front panel meets NEMA 4X/IP65 specifications for
indoor use when properly installed. Installation Category II, Pollution Degree
2. Panel gasket and keps nuts included.
A variety of communication protocols are available for the PAX and MPAX
Crimson is a Windows
The SFPAX is a Windows
Bulletin.
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-12 AWG copper wire
Maximum Torque: 5-7 inch-lbs (0.58-0.81 N-m)
REAL-TIME
CLOCK
YES
-
-
-
-
CAUTION: DISCONNECT ALL POWER BEFORE
INSTALLING OR REMOVING MODULE
* For detailed module and plug-in card specifications,
see corresponding PAX literature. (i.e. For MPAXI
specifications, see the PAXI literature)
®
®
based program that allows configuration of the
based program that allows configuration of the
PAXCDC1C - RS485 Serial (Connector)
PAXCDC2C - RS232 Serial (Connector)
PAXCDC4C - Modbus (Connector)