C200H-OC221 Omron, C200H-OC221 Datasheet - Page 94

no-image

C200H-OC221

Manufacturer Part Number
C200H-OC221
Description
I/O Module
Manufacturer
Omron
Datasheets

Specifications of C200H-OC221

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Outputs
8
No. Of Digital Outputs
8
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Specifications
Triac Output Unit C200H-OA223
Circuit Configuration
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
80
Internal
circuit
Output indicator
Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
250 VAC max.
(1.2 A max. 4 A/Unit)
F indicator
Fuse blowout
detection circuit
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 250 V (5.2-dia.x20)
N/A
300 g max.
E-shape
L
L
L
L
L
L
L
L
COM
NC
Fuse
0
1
2
3
4
5
6
7
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
COM
OUT
OUT
250 VAC max.
L