MPAXP000 Red Lion Controls, MPAXP000 Datasheet - Page 32

Process Input Module

MPAXP000

Manufacturer Part Number
MPAXP000
Description
Process Input Module
Manufacturer
Red Lion Controls
Datasheets

Specifications of MPAXP000

Accessory Type
Analog Input Module
Signal Input Type
Process/Control
No. Of Analog Outputs
5
No. Of Analog Inputs
5
Accuracy
0.03% of reading +2 μA, 0.03% of reading +2 mV
Brand/series
MPAX Series
Display Type
LED
Impedance, Input
20 Ohms to 500 Kiloohms
Measuring Range
-2 to 26 mA, -1 to 13 VDC
Resolution
16 Bit
Standards
cULus Listed, CE Certified
Voltage, Working
85 to 250 VAC
Sealing
NEMA 4/IP65
For Use With
EPAX 5 Digit Displays
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
and any option cards be assembled first. This will allow you the
opportunity to insure all the boards are fitted properly into their
connectors.
Installing the Option Cards
cards, they should be installed into the
MPAX before it is installed into the
LPAX Display. Refer to the
literature enclosed with the option
cards for installation instruction.
Installing the MPAX
align the module with the opening
in the LPAX case, as illustrated.
The module must be oriented as
shown, with terminal #1 toward the
top of the LPAX case. Carefully
slide the module into the LPAX case.
The LPAX and MPAX connectors will begin
to engage about
apply a small amount of pressure to the rear of the
MPAX module to fully engage the connection. Be sure the
module fully snaps into the slots at the rear of the LPAX case. The
display is ready for installation.
Removing The MPAX Module
remove all power and load circuits. Then insert a flat
screwdriver blade (
between the LPAX rear cover plate and the
module’s plastic cover as illustrated in Figure
2. Twist the screwdriver in the direction
shown to disengage the internal
connectors
squeezing and pulling back
on the rear finger tabs
(top
Carefully slide the
module out of the
LPAX case, keeping it
properly aligned with
the case opening.
1.0 ASSEMBLING THE DISPLAY
Prior to installing the LPAX Display, it is recommended that the MPAX
If your application requires option
To install the MPAX Module,
To remove the MPAX Module from the LPAX Display, first
and
CAUTION: The MPAX main circuit board and the option cards
bottom).
contain static sensitive components. Before handling the module
or the cards, discharge static charges from your body by
touching a grounded bare metal object. Handle the module by
the rear plastic cover only, and the option cards by the board
edges. Dirt, oil or other contaminants that contact the circuit
boards or components can adversely affect circuit operation.
while
¼"
from the bottom. At this point,
3
/
16
" or
firmly
1
/
4
") into the narrow slot
Figure 1, Installing an MPAX Module and Option Cards
Figure 2, Removing an MPAX Module
3
Installing the Labels
labels must be applied to the rear of the LPAX in the positions shown in the
drawing.
Each option card and the MPAX are shipped with a connection label. These
NOTE: All module and option card labels must be installed as
WARNING: Exposed line voltage exists on the MPAX main circuit
shown for safety purposes.
board and the option cards. DO NOT apply power to the
module OR load circuits until the module is properly installed
in the LPAX case.

Related parts for MPAXP000