Specifications of B2

Accessory Type
16 Position Mounting Board
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Supply Voltage
5V
Communication
Full Duplex, Two Twisted Pairs, Signal Common Wire, and Shield
Data Rate
300, 600, 1200, 2400, 4800, 9600, 19200, and 38400 Baud
Interface
RS-422⁄485
Led Position
Power, Receive, and Transmit
Mounting Type
Rack
Number Of Channels
16
Power Source
5
Special Features
Serial Communications
Temperature, Operating
0 to +70 °C
For Use With
Optomux Protocol
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
DATA SHEET
Form 463-050728
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Power Requirements
at 0.5 amps.
supply to several locations, better noise immunity is obtained by
having separate power supplies at each physical location where
a rack/brain board unit is installed. The +5 VDC power supply is
connected to the I/O mounting rack beneath the removable brain
board portion of the digital Optomux unit.
to power the analog I/O modules. The amount of power required
depends on the type and number of analog I/O modules that are
plugged into the Optomux unit. See the data sheets for your
modules; power requirements for each module are included in the
module specifications.
supply that can be used for powering a 4–20 mA current loop
using 4–20 mA analog I/O modules. For this type of application,
the +24 volt supply is required in addition to the supplies mentioned
Installation and Wiring
The B1 and B2 brain boards require +5 volts DC (± 0.1 VDC)
Although it is possible to distribute DC from a common power
Analog racks also require +15 VDC and -15 VDC (± 0.25 VDC)
Analog racks also provide terminals for a separate +24 volt
Power Supply Wiring
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
above. Refer to the module’ s data sheet for information on wiring
4–20 mA modules with a loop supply.
only for the modules. To determine what size power supply is
needed, add the load requirements for each module to determine
total power supply requirements.
Isolated supplies reduce the risk of ground loops in the
communication wiring. Do not connect the power supply’s DC
common to earth ground. Linear power supplies are recommended.
Connecting the Power Supply
“+ 5V” and “GND” on the mounting rack. If the + 5-volt supply is
used by more than one unit or by other devices, make sure the
voltage at each rack is 5 VDC (± 0.1 V).
any high-voltage field wires. There should only be one “earth”
The current requirements given for the output modules are
NOTE: Use only isolated supplies with Optomux products.
The diagram below shows how to connect the power supply.
Connect 5-volt power to the barrier strip connectors marked
The +5-volt and ±15-volt wires should be routed away from
BRAIN BOARDS
ANALOG AND DIGITAL
CLASSIC
page 4/10