6-Y-1-2-RMF-PM-115A EATON CUTLER HAMMER, 6-Y-1-2-RMF-PM-115A Datasheet - Page 86

Electromechanical Totalizing Counter

6-Y-1-2-RMF-PM-115A

Manufacturer Part Number
6-Y-1-2-RMF-PM-115A
Description
Electromechanical Totalizing Counter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of 6-Y-1-2-RMF-PM-115A

No. Of Digits / Alpha
6
Digit Height
4.8mm
Power Consumption
7W
Mounting Type
Panel
Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Counter Supply Voltage
115VAC
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54
54.3
General Specifications, continued
Description
Data Retention
Memory type
Duration
Signal Input
Rate/process time
Sensor type
Input impedance
Thresholds
Magnetic pickup range
Frequency response
Program Enable Input
Sensor type
Input impedance
Thresholds
Response
Accessory Power Output
Voltage
Current
Protection
Optional Outputs
Relay board
Analog retransmission
RS-485 serial communications
Environmental
Operating environment
Temperature
Humidity
Vibration
Shock
EMC
Front panel
CE EMC immunity and emissions requirements
Pollution degree 2
86
High
Low
High
Low
Number of relays
Contact type
Contact rating
Isolation dielectric strength
Output signals
Accuracy
Isolation dielectric strength
Baud rate
Parity
Address range
Protocol
Isolation dielectric strength
Operating
Storage
Control Products Catalog CA08102001E—August 2010 www.eaton.com
Counters, Panel Meters, Tachometers and Timers
Tachometers/Ratemeters
Specification
EEPROM, no batteries required
100 years
Signal in
Sink or source, DIP switch selectable
4.75 kohms to +5 Vdc or 34.9 kohms to ground
3.5 to 28 Vdc
0 to 1.9 Vdc, for single ended signals
200 mV p-p to 65V rms into 34.9 kohms
200 Hz max. or 10 kHz max. (5V signals), DIP switch selectable
Sink only
4.75 kohms to +5 Vdc
3.5 to 28 Vdc
0 to 1.9 Vdc
25 ms max. (5V signal)
12 Vdc ±12%
75 mA max.
Short-circuit protected
Two
1 set Form C per relay
5A, 250 Vac or 30 Vdc
2300 Vac
4–20 mA (<750 ohms) and 0–10V (>2500 ohms)
0.13% full scale and 100 PPM /°C (and 0.07% full scale change over 4–20 mA load
ranges)
2300 Vac to signal inputs, relays and AC power inputs; 500 Vac to RS-485 and DC power
inputs
1200, 2400, 4800, 9600, or 19,200, programmable
Even, odd or no parity
00 to 99 decimal
Opto 22
2300 Vac to signal inputs, relays and AC power inputs; 500 Vac to analog outputs and DC
power inputs
Indoor use to 2000 meters
32 to 122°F (0 to 50°C)
–4 to 158°F (–20 to 70°C)
0 to 85% RH, non-condensing
2.5 Gs, 30 to 200 Hz
30 Gs, 11 ms half sinewave
Immunity to EN 50082-2 (heavy industrial)
Emissions to EN 50081-2 (heavy industrial)
NEMA 4X when mounted with gasket provided
Met using shielded wiring on the RS-485, analog output and pulse input/ power lines. The
shields were connected to earth ground at the Eclipse end of the shields.
Overvoltage category II
®
compatible

Related parts for 6-Y-1-2-RMF-PM-115A