XTAE007B10TD3E008 EATON CUTLER HAMMER, XTAE007B10TD3E008 Datasheet - Page 153

IEC Non-Reversing Starter

XTAE007B10TD3E008

Manufacturer Part Number
XTAE007B10TD3E008
Description
IEC Non-Reversing Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTAE007B10TD3E008

No. Of Phases
Single Or Three
Power Rating
3.5kW
Current Rating
7A
Operating Temperature Range
-25°C To +50°C
Mounting Type
DIN Rail
Overload Adjustment Current Max
8A
Overload Adjustment Current Min
1.6A
Supply Voltage Max
24VDC
Frame Size
Standard
Electronic Overload Relays up to 1500A, continued
Description
Electrical/EMC
Radiated emissions
Conducted emissions
ESD immunity
Radiated immunity
Conducted immunity
Fast transient immunity
Surge immunity
Power freq. magnetic field immunity
Electromagnetic field
Distortion IEEE 519
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Surge immunity
IEC 60947-4-1-Table 15
EN 55011 (CISPIR 11) Group 1, Class A, ISM
IEC 60947-4-1-Table 14
EN 55011 (CISPIR 11) Group 1; Class ISM
IEC 60947-4-1 (Table 13)
IEC 60947-4-1
IEC 61000-4-3
IEC 60947-4-1, IEC 61000-4-6
IEC 60947-4-1 (Table 13)
IEC 61000-4-4
IEC 60947-4-1 (Table 13)
IEC 61000-4-5 a Class 4
IEC 60947-4-1, IEC 61000-4-8
IEC 60947-4-1 Table 13, IEC 61000-4-3
IEC 61000-4-2, EN 61131-2
IEC 61000-4-4, EN 61131-2
IEC 61000-4-5, EN 61131-2
Volume 5—Motor Control and Protection CA08100006E—May 2011 www.eaton.com
Specification
45 mm
30 mHz to 1000 mHz
0.15 mHz to 30 mHz
±8 kV air, ±6 kV contact
10 V/m 80 mHz–1000 mHz
3 V/m from 1.4 to 2.7 gHz
80% amplitude modulated
1 kHz sine wave
140 dub (10V rms)
150 kHz–100 mHz
±4 kV using direct method
±2 kV using direct method
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
30 A/m, 50 Hz
10 V/m
5% THD max., 5th harmonic 3% max.
4 kV contact
8 kV air discharge
±2 kV using direct method
±2 kV line-to-ground (CM)
with accessory installed in expansion bay
IEC Contactors and Starters
XT IEC Power Control
55 mm
30 mHz to 1000 mHz
0.15 mHz to 30 mHz
±8 kV air, ±6 kV contact
10 V/m 80 mHz–1000 mHz
3 V/m from 1.4 to 2.7 gHz
80% amplitude modulated
1 kHz sine wave
140 dub (10V rms)
150 kHz–100 mHz
±4 kV using direct method
±2 kV using direct method
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
30 A/m, 50 Hz
10 V/m
5% THD max., 5th harmonic 3% max.
4 kV contact
8 kV air discharge
±2 kV using direct method
±2 kV line-to-ground (CM)
with accessory installed in expansion bay
27.1
V5-T27-153

Related parts for XTAE007B10TD3E008