CV500ETN01 Omron, CV500ETN01 Datasheet - Page 231

no-image

CV500ETN01

Manufacturer Part Number
CV500ETN01
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500ETN01

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Error Log
206
03C2
03C3
Error
code
FINS/TCP packet discarded
FINS/UDP packet discarded
Meaning
01 to 10:
Connection
number
00
1st byte
Detailed error code
02:
Reopened
because
remote node
closed
03:
Reopened
because of
reception
error
04:
Reopened
because of
transmission
error
05:
Reopened
because RST
received from
remote node
06:
Reopened
because of
no keep-alive
response
07: Illegal
FINS/TCP
procedure
08: Insuffi-
cient mem-
ory during
server pro-
cessing
09: Insuffi-
cient mem-
ory during
client pro-
cessing
0A: Insuffi-
cient mem-
ory during
node switch-
ing
01 to FE:
Transmission
source node
address
2nd byte
Have the FINS/TCP connection
status checked when a
SEND(090), RECV(098), or
CMND(490) instruction is exe-
cuted in the ladder program.
Refer to Operation Manual, Con-
struction of Applications: SEC-
TION 7, and correct the remote
node (application on a personal
computer).
There is too much load (traffic) on
the Ethernet Unit. Correct the sys-
tem so that traffic is not concen-
trated.
The automatic generation (static)
method was used as the IP
address conversion method, so
remote IP address information in
internal memory could not be
changed.
Correction
Section 8-3
---
---
---
---
PROM
EE-

Related parts for CV500ETN01