Using FINS Applications
134
CX-Programmer/CX-Integrator
Ethernet port
Ethernet (Network number: none)
Node number: 1
IP address: 192.168.250.1
FinsGateWay Version 2003
FINS/TCP method
System Configuration Example 3: Connecting the CX-Programmer Online
Using the FINS/TCP Method
3. Starting FinsGateway ETN_UNIT Service
Select ETN_UNIT from Services under the Basic Tab in the FinsGateway
Setup Window, and then click the Start Button.
In this example, an online connection is made by FINS/TCP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/TCP method
CX-Programmer's Change PLC Dialog Box
PLC name
Network classification
Network Tab
• Node address:
• IP address:
• Destination port number:
• Keep-alive setting:
Settings for target PLC (PLC1)'s Change PLC Dialog Box
Ethernet Unit
FINS destination
Frame length
Response monitor time
IP address conversion: Automatic generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Set the remote FINS node address.
Set the remote IP address.
Set the FINS/TCP port number for the remote node.
Normally the PLC's default setting of 9600 should be
specified.
Sets the keep-alive function. Normally this should be
selected.
Target: PLC1
Network number
Node address
PLC1
FinsGateway
0
2
2,000 bytes
2 seconds
Section 6-5
Setting