4-4-2 Installation in Electrical Conduit
Connector attached on site
Connector already attached
Connector Attachment
y
Note Be sure to protect the connector on Optical Fiber Cords or Cables that have con-
19 to 21 mm
25 to 27 mm
25 to 27 mm
32 to 33 mm
Outer Diame-
nectors attached. In particular, use a protective cap to prevent the tip of the con-
nector from being contaminated by dirt.
Use a steel conduit, high or low-relief PVC pipe, or flexible plastic pipe. Use a
conduit with a diameter taken from the following table.
The inside of the conduit should be smooth, without any projections or joints
that might impede the cord or cable. Install just one Optical Fiber Cord or
Cable in a conduit.
The length of the conduit should be no more than 25 meters when the con-
duit is straight and level. When the conduit has bends along its path, the
overall length should be approximately 20 meters or less. When the route is
vertical, pull boxes (about 200
vals of approximately eight meters.
In the following diagram P.B. indicates a pull box.
Use a pre-bent piece of pipe or bend the conduit with a pipe bending tool.
The radius of the bend should be at least six times larger than the internal
t
ter
16 mm
22 mm
22 mm
28 mm
Inner Diame-
t
ter
16
22
22
28
Thick wall
Electrical Conduit
300
P.B
P.B
P.B
P.B
700 mm) should be installed at inter-
Approx. 8 m
Approx. 25 m
Approx. 20 m
19
25
25
31
Thin wall
Optical Fiber Cord only
Optical Fiber Cord or
Cable
Optical Fiber Cord only
Optical Fiber Cord or
Cable
Application
pp
Section 4-4