... VAC Ordering Information List of Models Phase-sequence Phase-loss Relay Phase sequence and phase loss monitoring Note: The power supply is shared with the rated input voltage. Cat. No. N145-E1-02 Functions Rated input voltage (See note.) 200 to 500 VAC Phase-sequence Phase-loss Relay Model K8AB-PH1 K8AB-PH 1 ...
Page 2
... Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact Munsell 5Y8/1 ABS resin (self-extinguishing resin) UL94-V0 Approx. 110 g Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N·m) 22.5 (W) 90 (H) 100 (D) mm K8AB-PH Cat. No. N145-E1-02 ...
Page 3
... Note: 1. Motor load phase loss cannot be detected. To detect motor load phase loss, use the K8AB-PM or K8AB-PA. 2. The K8AB-PH output relay is normally operative and L3 function both as the power supply terminals and as input terminals. If the voltage drops below the minimum input voltage (60%), then the Relay will not operate due to an undervoltage ...
Page 4
... Connect using L1, L2, and L3. Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase sequence is incorrect. 2. Outputs Terminals 11, 12, and 14 are output terminals for SPDT. Dimensions Phase-sequence, Phase-loss Relays K8AB-PH1 4 Phase-sequence Phase-loss Relay Indicators Item Terminal block Power indicator (See notes 1 and 2 ...
Page 5
... Using this product for thyristor controls or inverters will result in errors. 6. When setting the volume, adjust the control from the minimum side to the maximum side. Phase-sequence Phase-loss Relay K8AB-PH 5 ...
Page 6
... As the graph shows, voltage is induced at the motor terminals even if there is phase loss for a motor load, so the K8AB-PH1 cannot detect phase loss for motor loads during operation. Use the K8AB-PH1 to detect phase loss at startup. ...
Page 7
... Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority ...
Page 8
Cat. No. N145-E1-02 12/06 Specifications subject to change without notice Printed in USA ...