704.910.4 EAO, 704.910.4 Datasheet - Page 81

SWITCHING ELEMENT, 2NC, 10A, SCREW

704.910.4

Manufacturer Part Number
704.910.4
Description
SWITCHING ELEMENT, 2NC, 10A, SCREW
Manufacturer
EAO
Datasheet

Specifications of 704.910.4

No. Of Poles
2
Contact Current Max
10A
Contact Voltage Ac Max
500V
Contact Voltage Dc Max
250V
Switch Terminals
Screw
Circuitry
DPDT-2NC
For Use With
EAO Switch 04 Series Pushbutton Switches
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Technical Data
>
Switching system
Material
Mechanical characteristics
0
Electrical characteristics
Snap-action switching element PIT
SEV
UL
Declaration of conformity
CE
The double-break, snap-action switching element is equipped with
one or two independent contact systems, acting as normally open
or normally closed contact. The snap-action switching element is
fitted with self-cleaning contacts.
Up to three switching elements can be snapped to each actuator.
Snap-action switching elements are not permissible for emergency-
stop pushbuttons!
Material of contact
Hardsilver and gold-silver
Switch housing
Polycarbonate (PC)
Terminals
PIT Spring terminal
Skinning 8 mm
Wire cross-section:
Wire 0.2 to 1.0 mm²Stranded wire 0.2 to 1.0 mm² without core and
sleeve
Stranded wire 0.2 to 0.75 mm² with core and sleeve
Tightening torque
Screws at the mounting flange max. 25 Ncm
Actuating force
1 Normally closed 1.9 N
1 Normally open 2 N
Actuating travel
5.8 mm ± 0.2 mm
Rebound time
≤3 ms
Mechanical lifetime
(with 1 switching element)
Pushbutton maintained action
Pushbutton momentary action
Selector switch maintained action 1.25 million Cycles of operation
Selector switch momentary action 2.5 million
Emergency-stop switch
Keylock switch maintained action 25 000
Keylock switch momentary action 50 000
Standards
The switches comply with EN IEC 60947-1 / EN IEC 60947-5-1
Rated Insulation Voltage U
500 VAC / 600 VDC, as per EN IEC 60947-5-1
Contact resistance
New state ≤50 mΩ as per DIN IEC 60512-2-4
i
1.5 million
3 million
50 000
Cycles of operation
Cycles of operation
Cycles of operation
Cycles of operation
Cycles of operation
Cycles of operation
0
0
0
0
Environmental conditions
Approvals
Isolation resistance
≥10 MΩ between open contacts at 500 VDC, as per DIN IEC 60512-
2-10
Electrical life
50 000 cycles of operations
Conventional free air thermal current I
6 A, as per EN IEC 60947-5-1
the maximum current in continuous operation and at ambient
temperature must not exceed the quoted maximum values.
Switch rating
At switch rating AC for gold-silver and hardsilver contacts, service
category AC-15, as per EN IEC 60947-5-1 (cosφ 0.3)
Voltage
Current
At switch rating DC for gold-silver and hardsilver contacts, service
category DC-13, as per EN IEC 60947-5-1
Voltage
Current
Recommended minimum operational data
Gold-silver contacts:
Voltage
Current
Hardsilver contacts:
Voltage
Current
Protection class
Indicators and switches, fit for mounting into devices with protection
class II
Storage temperature
-40 °C ... +85 °C
Operating temperature
-40 °C ... +55 °C
Protection degree
IP 20
Shock resistance
(single impacts, semi-sinusoidal)
300 m/s²puls width 11 ms, as per EN IEC 60068-2-27
Vibration resistance
(sinusoidal)
100 m/s² at 10 Hz ... 500 Hz, as per EN IEC 60068-2-6 and EN
61373 Increased broad band noise, class 1B
Approbations
CB (IEC 60947)
CCC
CSA
Germanischer Lloyd
GOST
NFF 16-102
Declaration of conformity
CE
250 VAC
6 A
24 VDC
6 A
24 VDC
5 mA
24 VDC
50 mA
110 VDC
1.0 A
th
07.2010
79
04

Related parts for 704.910.4