H3CR-A8 24-48VAC/12-48VDC Omron, H3CR-A8 24-48VAC/12-48VDC Datasheet - Page 50

TIMER, ON-DELAY

H3CR-A8 24-48VAC/12-48VDC

Manufacturer Part Number
H3CR-A8 24-48VAC/12-48VDC
Description
TIMER, ON-DELAY
Manufacturer
Omron

Specifications of H3CR-A8 24-48VAC/12-48VDC

Contact Configuration
DPCO
Nom Input Voltage
48V
Delay Time Range
0.05s To 300h
Adjustment Type
Knob
Relay Mounting
Panel
Svhc
Hexabromocyclododecane (HBCDD) And All Major Diastereoisomers Identified
Timing Adjustment
Knob
H3CR
Relationship between Input and Power Supply
Circuits (H3CR-Aj/-AjS)
An appropriate input is applied to the input signal terminals of the
H3CR-Aj/-AjS when one of the input terminals is short-circuited
with the common terminal (terminal 2) for the input signals. Never
use terminal 10 as the common terminal for this purpose, otherwise
the internal circuit of the Timer will be damaged.
Do not connect a relay or any other load between input terminals,
otherwise the internal circuit of the Timer will be damaged due to the
high-tension voltage applied to the input terminals.
Relationship between Input and Power Supply
Circuits (H3CR-AP)
Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned ON or OFF irrespec-
tive of the ON/OFF state of the power supply.
It must be noted that a voltage equivalent to the power supply volt-
age is applied to the input circuit.
52
Incorrect
Correct
AC or DC
power supply
AC/DC
power
supply
Input
contact
H3CR-AP
Input circuit
Ry
Input terminal
Input terminal
Input terminal
5, 6, 7
G, S, R
5, 6, 7
G, S, R
5, 6, 7
G, S, R
Power supply
circuit
H3CR-A
H3CR-A
H3CR-A
10
2
10
2
10
2
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
be different in phase or the terminals will be short-circuited to one
another (refer to the figures below).
Common to All H3CR-A Models
With the H3CR-AP, input wires must be as short as possible. If the
floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables
with 120 pF/m), the operation will be affected. Pay particular atten-
tion when using shielded cables.
The H3CR-AjS transistor output is isolated from the internal cir-
cuitry by a photocoupler. Therefore, either NPN or PNP output is
possible.
Incorrect
Correct
Contact or transistor for
external input signal
Contact or transistor for
external input signal
6
7
6
7
6
7
6
7
H3CR-AP
H3CR-AP
H3CR-AP
H3CR-AP
10
2
10
2
10
2
2
10
Short-circuit current
Short-circuit current
Power supply
Power supply
H3CR

Related parts for H3CR-A8 24-48VAC/12-48VDC