DS450-3 Emerson Network Power, DS450-3 Datasheet - Page 2

PWR SUP 12V 450W 1U X 2U X 11"

DS450-3

Manufacturer Part Number
DS450-3
Description
PWR SUP 12V 450W 1U X 2U X 11"
Manufacturer
Emerson Network Power
Series
DS450r
Datasheet

Specifications of DS450-3

Operating Temperature
-10°C ~ 50°C
Power (watts) - Rated
444W
Efficiency
84%
Approvals
CCC, CE, cUL, EN60950, NEMKO, UL
Line Regulation
-3% ~ 5%
Load Regulation
-3% ~ 5%
Voltage - Output
12V
Number Of Outputs
1
Power (watts)
450W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
90 ~ 264VAC
Mounting Type
Rack Mount
1st Output
12 VDC @ 37A
Size / Dimension
12.03" L x 3.07" W x 1.57" H (305.6mm x 78mm x 40mm)
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
12V
Output Current
37A
Power Rating
450W
Input Voltage
90V AC To 264V AC
Length
305.6mm
Width
78mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
2nd Output
-
3rd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
454-1432

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
DS450-3
Manufacturer:
IR
Quantity:
1 000
Environmental Specifications
Operating temperature:
Storage temperature:
Altitude, operating:
Electromagnetic
susceptibility / Input transients:
RoHS & lead-free compliant (no tantalum caps)
Humidity:
Shock and vibration specificatons complies with Emerson Network Power Std. Specification, Q3205
MTBF (Demonstrated):
Logic Control
PS Inhibit:
PS_Status:
AC_Pfail:
Fan_Fault:
Tach_1:
Ordering Information
*Overcurrent latches off if overcurrent lasts over 1 second, otherwise it is auto recovery.
*For 5 Vsb, consult marketing.
DS450-3
DS550-3
Output
Voltage Set Point
Nominal Output
12.0 Vdc
12.0 Vdc
3.3 Vsb
3.3 Vsb
When supply is inserted into the system the pin is pulled LOW and power supply is ON after all other pins are
seated
I
due to -PS_ON, PS_KILL, or a fault, then P6 is high.
I
failure (AC missing or too low for power supply operation). If the supply is turned off due to -PS_ON, PS_KILL,
or a fault, then P7 remains high.
The PSU will provides an open collector Tach 1 output.
This signal is generated from the fan. The signal should generate 2 pulses per revolution. The logic in the
system will be operating at 3.3 V.
2
2
C port P6. When the power supply is on and running normal P6 is low. When the power supply is off, either
C port P7. P7 is high except when the power supply turns the main outputs, not +3.3 Vsb, off due to an AC
-10 °C to 50 °C
-40 °C to +70 °C
10,000 ft.
-EN61000-3-2, -3-3
-EN61000-4-2, 4.3, 4-4, -4-5, 4-11 Level
-EN55024:1998
20 to 90% RH, non-condensing
400K Hrs at full load, 40 °C
Tolerance
Set Point
± 0.2%
± 0.2%
± 1%
± 1%
Regulation
+5 / -3%
+5 / -4%
+5 / -3%
+5 / -4%
Total
Minimum
Current
0 A
0 A
0 A
0A
Maximum
Current
37.0 A
45.0 A
3.0 A
3.0 A
Output Ripple
120 mV
120 mV
60 mV
60 mV
Embedded Power for
Business-Critical Continuity
P/P
4.9 A Avg, 7 A max
4.9 A Avg, 7 A max
39.5 A - 44.4 A
48.0 A - 54.0 A
Overcurrent
Rev. 03.15.11_82
DS450/DS550
2 of 4

Related parts for DS450-3