VPL24-1100 Triad Magnetics, VPL24-1100 Datasheet

Transformers 24V@1.04A 12V@2.08A 25VA

VPL24-1100

Manufacturer Part Number
VPL24-1100
Description
Transformers 24V@1.04A 12V@2.08A 25VA
Manufacturer
Triad Magnetics
Type
Power Transformersr
Series
Worldr
Datasheets

Specifications of VPL24-1100

Power Rating
25 VA
Product
Transformers - Miscellaneous
Brand/series
World Series™/VPL Series
Configuration
Bobbin
Current, Secondary
2.08/1.04 A
Dimensions
3.125"W×1.937"H×2.125"D
Frequency
50/60 Hz
Length, Lead
8 "
Mounting Hole Centers
2.812 "
Mounting Type
Panel/Chassis
Number Of Outlets
2
Phase
1
Power, Rating
25 VA
Standards
UL
Termination
Leadwires
Voltage, Primary
115/230 VAC
Voltage, Secondary
12/24 VAC
Weight
1.3 lbs.
Mounting Style
Foot
Height
1.937 in
Length
3.25 in
Termination Style
Wire Leads
Width
2.125 in
Current Rating
2.08A
Transformer Mounting
Chassis
Peak Reflow Compatible (260 C)
Yes
Transformer Type
Power
Supply Voltage
230V
Output Voltage
12V
Output Current
2.08A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
VPL24-1100
Electrical Specifications (@25C)
1. Maximum Power: 25.0VA
2. Input Voltage – Series: 230VAC @ 50/60Hz, Parallel: 115VAC@
3. Output Voltage – Series
4. Voltage Regulation: 20% TYP @ full load to no load
5. Hipot: 3500VAC between primary to secondary and windings to core.
6. Recommended Fuse
Construction:
Dual winding construction with an insulated shroud, both made of a high temperature
material that exceeds UL flammability requirements. Shrouds are provided over the
connections of the leads to the windings on both primary and secondary coils. Devices are
designed with a minimum of 6mm creepage distance between the primary and secondary
and are manufactured with a Class B (130°C) insulation system.
Agency Files:
UL File: E65390, UL 5085-1 and 3 (formerly UL1585), Class 2/3
cUL: File E65390, For Canadian Use (CSA 22.2, No.66.1-06 and No.66.3-06)
T UV Certificate No.: R72072385, EN60950, Information Technology
Dimensions:
1.937
Weight: 1.3 lbs.
Connections
Input: Series – BLK to BLU, Jumper WHT to BRN
Output: Series – RED to GRY, Jumper YEL to VIO
RoHS Compliance: As of manufacturing date February 2005, all standard products meet the
requirements of 2002/95/EC, known as the RoHS initiative.
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’
website for the most current version.
1
2
3
4
intended to be used independently.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
Non-Inherently limited. Class 3.
Non-Inherently limited. Class 2 not wet, Class 3 wet.
Fuse must be used on secondary as conditions of acceptability for UL Class2/3 operation.
Primary and secondary windings are designed to be connected in series or parallel. Winding are not
A
3.250
Parallel – BLK to BLU, Jumper BLK to BRN and WHT to BLU
Parallel – RED to GRY, Jumper RED to VIO and YEL to GRY
B
Series: Littelfuse p/n 313 1.25HXP, 1.25A 250V, slow blow, ¼ x 1 ¼ or,
Parallel: Littelfuse p/n 313 2.5HXP, 2.5A 250V, slow blow, ¼ x 1 ¼ or,
4
:
2.125
C
Cooper Bussmann p/n BK/MDL-1 ¼, 1.25A 250V, ¼ x 1 ¼
Cooper Bussmann p/n BK/MDL-2 ½, 2.5A 250V, ¼ x 1 ¼
3
:
1
2.812
: 24.0V CT@ 1.040A, Parallel
D
Units: In inches
8.00
E
22520B Temescal Canyon Road
Corona, California
92883
0.187
F
2
: 12.0V @ 2.080A
P
Chassis Mount : International Series
O W E R
50/60Hz
T
Publish Date: October 26, 2009
R A N S F O R M E R
F
A
BRN
WHT
BLU
BLK
SCHEMATIC
B
D
RED
YEL
GRY
VIO