E8MS-N0 Omron, E8MS-N0 Datasheet

SENSOR PRESSURE NEGATIV 0-101KPA

E8MS-N0

Manufacturer Part Number
E8MS-N0
Description
SENSOR PRESSURE NEGATIV 0-101KPA
Manufacturer
Omron
Series
E8MSr
Datasheets

Specifications of E8MS-N0

Pressure Type
Gauge
Operating Pressure
-14.65 ~ +0 PSI, -101 ~ 0 kPa
Port Size
Male, 1/8" (3.175mm) 27 NPT
Output
Digital
Voltage - Supply
12 V ~ 24 V
Termination Style
Cable
Operating Temperature
0°C ~ 50°C
Package / Case
Module
Sensor Output
Voltage
Supply Current
25mA
Voltage Rating
12V
Port Style
NPT, M5
Pressure Measurement Type
Gage
Operating Pressure Min
0psi
Terminal Type
Connector
Operating Pressure Max
14.6psi
Mounting Style
Desktop
Maximum Operating Temperature
+ 50 C
Minimum Operating Temperature
0 C
Operating Supply Voltage
12 V
Output Voltage
1 V to 5 V
Pressure Port
Y
Sensor Type
Sensors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E8MSN0
Four-channel Pressure Sensor Offers
Versatile Functions and High Precision
Without Errors
H
H
H
H
H
Ordering Information
J SENSORS
E8MS
E8M
J CONTROLLER
Type
Positive pressure sensor
Positive pressure sensor
Negative pressure sensor
Type
Minute differential pressure sensor
Positive pressure sensor
Negative pressure sensor
Item
Controller
Controller
Pressure Sensor
The industry’s smallest pressure sensor,
compact, lightweight — ideal for robot arms
or other moving components
A highly sensitive minute-pressure sensor
model detects very small differences in air
pressure
Requires no wiring conduit — can be
located for sensing in small places
Simple display panel efficiently saves
space, but offers large LEDs
Easy sensitivity adjustment using the teach
function and channel-to-channel copy
function
R
Pressure range description
0 to 100 kPa (0 to 14.5 psi)
0 to 1 MPa (0 to 145 psi)
0 to - - 101 kPa (0 to - - 14.6 psi)
Pressure range description
Differential pressure from 0 to 1,000 Pa
(0 to 0.145 psi) between positive and
negative ports
0 to 1 MPa (0 to 145 psi)
0 to - - 101 kPa (0 to - - 14.6 psi)
Description
Optional for pressure sensors:
Optional for pressure sensors:
E8M series and E8MS series
2
Part number
E8MS-01
E8MS-10
E8MS-N0
Part number
E8M-A1
E8M-10
E8M-N0
Part number
K3C-MP8-T1Z
K3C MP8 T1Z
E8M/E8MS

Related parts for E8MS-N0

E8MS-N0 Summary of contents

Page 1

... MPa (0 to 145 psi 101 kPa ( 14.6 psi) Description Optional for pressure sensors: Optional for pressure sensors: E8M series and E8MS series 2 E8M/E8MS Part number E8MS-01 E8MS-10 E8MS-N0 Part number E8M-A1 E8M-10 E8M-N0 Part number K3C MP8 T1Z K3C-MP8-T1Z ...

Page 2

... Instruction manual E8MS- MPa (0 to 145 psi) 1.5 MPa (217.5 psi (approx. 50G) for 3 times each and Z directions. 3 E8M/E8MS Part number E89-M3 E89-M4 XS8A-0442 K32-MP2W Y92A-48F1 Y92A-48 E8MS- 101 kPa ( 14.6 psi) 400 kPa (58 psi) (approx. 5G) for 8 min for 10 times each in X, ...

Page 3

... NPT and M5 female screw Connector (use the E89-M3, sold separately) Approx (1.06 oz.) SUS304 Aluminum, polyether sulfonic resin Instruction manual Pressure generator 4 E8M/E8MS E8M- 101 kPa ( 14.6 psi) 400 kPa (58 psi) 2 (approx.10G) for 8 min for 4 times each male screw Approx (0.71 oz.) ...

Page 4

... MPa (0 to 14.5 psi 145 psi max. 30 VDC max. 0.8 V max. with a flow current 0.4 V max. with a flow current (approx. 30G) for 3 times each and Z directions. 5 E8M/E8MS E8MS-N0, E8M- 101 kPa ( 14.6 psi digits for a single channel digits ...

Page 5

... E8M/E8MS Engineering Data (Typical) J LINEAR OUTPUT VOLTAGE VS. PRESSURE E8MS-01 Pressure (kPa) E8MS-N0/E8M-N0 Pressure (kPa) J OUTPUT LINEARITY E8MS-01 Pressure (kPa) E8MS-N0/E8M-N0 E8MS-N0 E8M-N0 Pressure (kPa) E8MS-10/E8M-10 Pressure (kPa) E8M-A1 Differential pressure (Pa) between positive and negative ports E8MS-10/E8M-10 E8MS-10 E8M-10 Pressure (kPa) E8M-A1 ...

Page 6

... Voltage (V) E8M-10 Pressure 0 Rated pressure Voltage (V) E8MS-10 Pressure 0 Rated pressure Temperature (°C) E8M-10 Pressure 0 Rated pressure Temperature (°C) 7 E8M/E8MS E8MS-N0 Pressure 0 Rated pressure Voltage (V) E8M-N0 Pressure 0 Rated pressure Voltage (V) E8MS-N0 Pressure 0 Rated pressure Temperature (°C) E8M-N0 Pressure 0 Rated pressure Temperature (°C) ...

Page 7

... DISPLAY Used to select the measurement value, ON-point, or OFF- point display in measurement mode. Set menu or set value display is selected in set mode. 14. UP/Down Used to change the set values in set mode. The values increase by pressing the Up ( crease by pressing the Down ( 8 E8M/E8MS ) Key and de- ) Key. ...

Page 8

... E8M/E8MS Operation J OUTPUT CIRCUITS Sensor Output Configuration Linear Output E8MS-01, E8MS-10, E8MS-N0 Connector Brown Pressure Sensor main Black (linear output) circuit Load E8M-A1 Brown Power indicator (green) Pink Pressure Sensor main Black (linear output) circuit Load E8M-10, E8M-N0 Connector Brown Power ...

Page 9

... The following abbreviations are used for the digital display of the Controller. Abbreviation Meaning SET Setting UNT Unit OPE Operation SEN Sensor PRT Protect COP Copy HYS Hysteresis WID Width AUT Auto DSP Display AVE Average Measurement mode 1 s min. 10 E8M/E8MS Basic setting mode Special setting mode Teaching mode ...

Page 10

... Special Setting Mode Key-protect function for set value protection Data copy function to copy the data of channels Original pressure fluctuation compensation setting Hysteresis width Window width setting Measurement value display refresh interval setting Number of measurement times setting for measurement value averaging 11 E8M/E8MS ...

Page 11

... Refer to Key-protect Settings (found in the Advanced Operations Sub-Section) and disable the key-protect function. Select the Sensor type according to the target object. The following Sensor types are available. Model E8M- E8MS- 101 E8M-N0 E8MS-10 1000 E8M-10 Not connected --- ...

Page 12

... Press the MENU The display changes to Key once. “OPE.” Refernce Table for Sensor Types and Availability of Measurement Units Sensor type Pressure range Display unit Sensor type Pressure range kpa (kPa) E8MS- 101 kPa Yes E8M-N0 E8MS- MPa Yes E8M-10 E8M- 1,000 Pa Yes ...

Page 13

... Note: If the RST/ESC Key is pressed instead, the set values will not be entered, and “SET” will appear. When the OUT1 settings are finished and the DISPLAY Key is pressed, OUT2 will be ready for setting only with the channel that has OUT2 output. 14 E8M/E8MS ...

Page 14

... Pressure OFF point of OUT1 Press the Up or Down Key to change the set value. ON point of OUT2 Press the Up or Down Key to change the set value. Enter OFF point of OUT1 Press the Up or Down Key to change the set value. 15 E8M/E8MS ...

Page 15

... When the OUT1 settings are finished and the DISPLAY Key is pressed, OUT2 will be ready for setting only with the channel that has OUT2 output. Channel 1 Cancel Select with the Up or Down Key. Channels Cancel Select with the Up or Down Key. Window Mode NO output NC output Enter Select with the Up or Down Key. Enter 16 E8M/E8MS OFF point OFF point - - - Hysteresis ON point ON point - - - Hysteresis ...

Page 16

... If there is no key input for 2 s during set value display, the display panel will automatically return to the measurement value display. Channel 1 (In the Case of Example 1 on Page 15) ON point of OUT1 OFF point of OUT2 Channels (In the Case of Example 2 on page 15) ON point of OUT1 OFF point of OUT1 ON point of OUT2 OFF point of OUT1 17 E8M/E8MS ...

Page 17

... PLAY Key. By pressing the DISPLAY Key again, OUT2 will be ready for setting for channel 1 only. Two-point teaching mode One-point teaching mode (hysteresis mode teaching) (window mode teaching) Displayed items: TH1 (teach hysteresis mode, first point) TW (teach window mode) Two-point Teaching Pressure 18 E8M/E8MS ...

Page 18

... Note: The Controller will be in hysteresis mode automatically after two-point teaching. The above settings are useful for applications that check vacuum absorption. ON-point and Present OFF-point indicators measurement value flash. appears. Present measurement value appears. Teaching completed on the first point. Measurement mode Teaching completed on the second point. 19 E8M/E8MS ...

Page 19

... The present measurement value will be reset as zero by pressing the RST/ESC Key for 1 s. The possible zero-reset range is within ± the rated output. Otherwise, “ER.T” will appear and the present measurement value will not be reset. Press the RST/ESC Key for 1 s. Measurement mode Teaching completed. 20 E8M/E8MS ...

Page 20

... No key protect 1: No key protect in SET, UNT, zero-reset, or teaching operation, zero-reset, and all set modes. 2: Key protect in teaching operation. Hysteresis Original Fluctua- Width Change tion Compensa- Function tion Function Window Width Setting 21 E8M/E8MS Cancel Edit Use the Up or Down Key. ...

Page 21

... If the contents of channels are copied to channel 1, there will be no difference in data be- tween OUT1 and OUT2 of channel 1. Source channel appears. Destination channel appears. Copying Source channel change with the Up or Down Key. Execute copy Destination channel change with the CH Key. 22 E8M/E8MS ...

Page 22

... The width between the ON and OFF points are used as the hysteresis width in hysteresis mode. Therefore, the settings cannot be changed in the above steps pressing the DISPLAY Key after OUT1 is displayed, the display will change to OUT2 only with the channel that has OUT2 output. Enter Window Mode Changinghysteresis width Pressure ON point OFF point 23 E8M/E8MS ...

Page 23

... The set value will be entered and “AVE” will appear by pressing the MENU Key. If the RST/ESC Key is pressed, set value change will be canceled and “DSP” will appear. Note: The number of measurement times for measurement value averaging is set in the menu while “AVE” is displayed. Enter Enter 24 E8M/E8MS ...

Page 24

... Note: If 0.5 is set while “DSP” is displayed and 32 is set while “AVE” is displayed, pressure will be measured 32 times and averaged as a block. The averaged blocks as a mean value will be displayed and refreshed every 0.5 s. Cancel Value change with the Up or Down Key. Enter Enter 25 E8M/E8MS ...

Page 25

... Teaching input Error code flashes. range error Zero reset range Error code flashes. error Dimensions Unit: mm (inch) J SENSORS E8MS-01 M5, 7.5-mmdepth E8MS-10 E8MS-N0 15 (0.59) 13 (0.51) E8M-A1 4-mm-dia., 4-conductor (40 strands x 0.08 dia.), vinyl-insulated cord, length Error code Reset method Reset the power supply. ...

Page 26

... E89-M3 Sensor I/O Connector Cable for E8M (Sold separately) Includes one XS8A-0442 cable Connector. E89-M4 Sensor I/O Connector Cable for E8MS (Sold separately) Includes one XS8A-0442 cable Connector. 8.9 (0.35) Connection with E89-M3 Sensor I/O Connector 13 M5 ...

Page 27

... Use the Soft Cover, however, if the Controller operated with wet or oily hands. Although the Soft Cover conforms to IEC IP54F, do not install the Controller with the Soft Cover in places where oil may be directly sprayed onto the Controller. 28 E8M/E8MS 14.2 (0.56) 44.8 (1.76) ...

Page 28

... Sensor and Controller Combinations (LED lighting input) Use the Pressure Controllers in the following combinations. The E89-M3/M4 is required when using the Sensor as a single unit. Model E8MS-01 E8MS-10 E8MS-N0 E8M-A1 E8M-10 E8M-N0 Note: f: Required; ×: Not required. Sensor and Controller Connection E8MS-jj ...

Page 29

... Be sure to connect to the polarities of the power supply correctly and avoid incorrect wiring. Incorrect connection or wiring may result in breaking or burning. J CORRECT USE Connecting and Locking the E8MS Sensor I/O Con- nector (E89-M4) 1. Hold both ends of the female connector connected to the Sensor I/O Connector so that the protrusion on the female ...

Page 30

... Do not apply any tensile strength in excess of 20N (4.5 lbs) for E8MS, 30N (6.75 lbs) for E8M to the cables or connectors. Do not pull the cables. When removing the connectors for external connection, be sure to use the lock lever. ...