SMB500 GAMEWELL-FCI [Gamewell-FCI by Honeywell], SMB500 Datasheet - Page 2

no-image

SMB500

Manufacturer Part Number
SMB500
Description
Fault Isolator Module
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Examples of Device Counts
(see notes under Applications on page 1)
EXAMPLE 3
EXAMPLE 1
g2464ex1.wmf
Operation
Automatically opens circuit when the line voltage drops below four volts. Fault Isola-
tor Modules should be spaced between groups of addressable devices (maximum
25, see notes on page 1) in a loop to protect the rest of the loop. If a short occurs
between any two isolators, then both isolators immediately switch to an open circuit
state and isolate the groups of sensors between them. The remaining units on the
loop continue to fully operate.
In Style 4 loops, the SS-LI is generally used at each T-tap branch, to limit the effect of
short circuits on a branch to the devices on that branch. The LED indicator is on
continuously during a short circuit condition.
The SS-LI Fault Isolator Module automatically restores the shorted portion of the
communications loop to normal condition when the short circuit condition is removed.
g2464ex3.wmf
Northford, CT 06472-1610
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Phone: 203-484-7161
12 Clintonville Road
Fax: 203-484-7118
Gamewell-FCI
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell-FCI.
Page 2 of 2
Specifications
Operating voltage
Current range
Standby current
Pulsing current
Temperature range
Relative humidity
Weight
15 – 32 VDC (peak).
5 mA for LED latched in alarm.
400 µA maximum, plus supervi-
sion current.
30 mA for 15 mS.
32°F to 120°F (0°C to 49°C).
10% to 93%.
150 grams (5 oz.).
SS-LI
CS-2464 09/01/06
EXAMPLE 2
g2464ex2.wmf