SMB500 GAMEWELL-FCI [Gamewell-FCI by Honeywell], SMB500 Datasheet

no-image

SMB500

Manufacturer Part Number
SMB500
Description
Fault Isolator Module
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
SS-LI
Fault Isolator Module
The maximum number of addressable devices between isolators (or B224BI isola-
tor bases) is 25 devices. B224RB relay bases draw more current than other intelli-
gent devices. When calculating the 25-device maximum: B224RB represents 2.5
DEVICES
NOTE ON MAXIMUM NUMBER OF DEVICES: Up to 99 SS-LI modules and/or bases
an be used per Signaling Line Circuit (SLC) without loss of additional module ad-
dresses due to current limitations.
Installation
Product Line Information
SS-LI
SMB500
Construction
The face plate is made of off-white plastic. Includes yellow LED indicator that pulses
when normal and illuminates steady when a short is detected.
SS-LI CS-2464 09/01/06
Mount on a standard 4" (10.16 cm) mounting junction box which is at least
2-1/8" (5.3975 cm) deep.
Terminal screws are provided for “in and out” wiring.
Installation instructions are provided with each module.
Surface-mount box is available as an option.
SS-LI Fault Isolator Module
Isolator Module.
Surface Mount Backbox.
Description
The Gamewell SS-LI Fault Isolator
Module is used with the 602, 610,
632, 654, 658, 602VE, 610VE, VSYS-
1 thru IS-610 and 632-126 thru -1008
to protect the system against wire-
to-wire short circuits on the
SmartScan
Applications
The Fault Isolator Modules should
be spaced between groups of sen-
sors in a loop to protect the rest of
the loop. Use to isolate short circuit
problems within a section of a loop
so that other sections can continue
to operate normally. The SS-LI sup-
ports a maximum of 25 devices
inbetween isolators.
TM
SLC loops.
2243dia1.wmf
Page 1 of 2
Features
• Powered by SmartScan
• Mount in standard 4" (10.16 cm)
• Integral LED blinks to indicate
• High noise (EMF/RFI) immunity.
• Wide viewing angle of LED.
• SEMS screws with clamping
• Opens SLC loop automatically on
• Automatically resets on correction
• Supports Style 4, 6, or 7 wiring.
Listings
• UL Listed: file S1195.
loop directly, no external power
required.
square (2-1/8" [5.3975 cm] deep)
junction boxes.
normal condition. Illuminates
steady when short circuit condition
is detected.
plates for ease of wiring.
detection of short, preventing the
short from causing failure of the
entire loop.
of short.
Listings and approvals below
apply to the SS-LI Fault Isolator
Module. In some cases, the
module may not be listed by
certain approval agencies, or
listing may be in process. Consult
factory for latest listing status.
TM
SLC

Related parts for SMB500

SMB500 Summary of contents

Page 1

... Installation instructions are provided with each module. • Surface-mount box is available as an option. • Product Line Information SS-LI Isolator Module. SMB500 Surface Mount Backbox. Construction The face plate is made of off-white plastic. Includes yellow LED indicator that pulses when normal and illuminates steady when a short is detected. SS-LI CS-2464 09/01/06 Description ...

Page 2

Operation Automatically opens circuit when the line voltage drops below four volts. Fault Isola- tor Modules should be spaced between groups of addressable devices (maximum 25, see notes on page loop to protect the rest of the ...