AN19DN0A5E020 Eaton / Control Automation, AN19DN0A5E020 Datasheet - Page 12

no-image

AN19DN0A5E020

Manufacturer Part Number
AN19DN0A5E020
Description
NEMA STARTER, SIZE 1, WITH C440 ELECTRONIC OVERLOAD RELAY, (4-20A), FLA, 120VAC COIL
Manufacturer
Eaton / Control Automation
Datasheet

Specifications of AN19DN0A5E020

Lead Free Status / Rohs Status
RoHS Compliant part
Technical Data and Specifications
Electronic Overload Relays up to 1500A
Description
Electrical Ratings
Operating voltage (three-phase) and frequency
FLA Range
Use with Contactors
XT IEC frames
Freedom NEMA sizes
Trip Class
Motor Protection
Thermal overload setting
Feature
Phase loss
Phase unbalance (selectable: enable/disable)
Ground fault (selectable: enable/disable)
Reset
Indicators
Trip status
Mode LED
Options
Remote reset
Reset bar
Communication expansion module
Communication adapter
Capacity
Load terminals
Input, auxiliary contact and remote reset terminals
Voltages
Insulation voltage U
Insulation voltage U
Rated impulse withstand voltage
Overvoltage category/pollution degree
Terminal capacity
Tightening torque
Terminal capacity
Tightening torque
i
i
(three-phase)
(control)
Specification
45 mm
Range
690 Vac (60/50 Hz)
0.33–1.65A
1–5A
4–20A
9–45A
B, C, D
00, 0, 1, 2
10A, 10, 20, 30
Selectable
1.05 x FLA: does not trip
1.15 x FLA: overload trip
Range
Fixed threshold 50%
Fixed threshold 50%
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
Manual/automatic
Orange flag
One flash: Overload operating properly
Two flashes: Current is above FLA dial setting—pending trip
Yes
Yes
Yes
Yes
12–10 AWG (4–6 mm
8–6 AWG (6–16 mm
20–25 lb-in (2.3–2.8 Nm)
25–30 lb-in (2.8–3.4 Nm)
2 x (18–12) AWG
5.3 lb-in (0.8–1.2 Nm)
690 Vac
500 Vac
6000 Vac
III/3
Motor Protection and Monitoring
Control Products Catalog CA08102001E—June 2010 www.eaton.com
2
)
2
)
C440/ XT Electronic Overload Relay
55 mm
Range
690 Vac (60/50 Hz)
20–100A
F, G
3
10A, 10, 20, 30
Selectable
1.05 x FLA: does not trip
1.15 x FLA: overload trip
Range
Fixed threshold 50%
Fixed threshold 50%
50% of FLA dial setting
>150% = 2 sec
>250% = 1 sec
Manual/automatic
Orange flag
One flash: Overload operating properly
Two flashes: Current is above FLA dial setting—pending trip
Yes
Yes
Yes
Yes
6–1 AWG (16–50 mm
25–30 lb-in (2.8–3.4 Nm)
2 x (18–12) AWG
5.3 lb-in (0.8–1.2 Nm)
690 Vac
500 Vac
6000 Vac
III/3
2
)
42.1