E53-S Omron Automation, E53-S Datasheet - Page 8

no-image

E53-S

Manufacturer Part Number
E53-S
Description
Module; 4; 250 VAC; 1 A; 190 ms; UL Listed, CSA Certified, CE Marked
Manufacturer
Omron Automation
Type
I/Or
Datasheet

Specifications of E53-S

Brand/series
E5-K Series
Current, Input
1 A
Number Of Inputs
4
Primary Type
Expansion
Standards
UL Listed, CSA Certified, CE Marked
Time, Response
190 ms
Voltage, Input
250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
Micro Controllers
J Operating Parameters
Mode Selection
J Parameters And Menus - - For Setting The Controller
Press the Display Key for 1 sec. min. to switch to modes other than
the manual or protect mode.
The figure below (Menu Display) shows all modes in the order that
they are displayed. Some parameters are not displayed, depending
on the protect mode setting and the option boards used.
Limits use of the menu and A/M Keys.
The protect function prevents unwanted modification of parameters and can also be used to prevent switching between
the auto and manual operation.
Sets the controller to manual operation mode.
You can only manually adjust the manipulated variable (MV) in this mode.
For normal operation.
Change: the set point during operation, and start or stop Controller operation; and, (only in this mode) monitor the
process value, ramp SP, and manipulated variable.
For adjusting primary control parameters.
Execute: AT (auto-tuning); set alarm values; set the control period; and, set PID parameters.
For adjusting secondary control parameters.
Set parameters for: limiting the manipulated variable and set point; switch between the remote and local modes; set the
loop break alarm (LBA), alarm hysteresis, and the digital filter value of inputs.
For setting the basic specifications.
Set parameters for: input type, scaling, output assignments and direct/reverse operation.
For setting expanded functions.
Set: ST (self-tuning), SP setting limiter. Select: advanced PID or ON/OFF control. Specify the standby sequence
resetting method. Initialize parameters; and, set the time for automatic return to the monitoring display.
For setting option functions.
Set: the communications conditions; transfer: output and event input parameters to match the type of Option Board
installed in the Controller. This mode will be accessible only when an option board is installed in the controller.
For calibrating inputs and transfer output.
Calibrate the selected input type. Transfer output can be calibrated only when the Communications Unit (E53-CKF) has
been installed in the Controller.
1 second min.
1 second min.
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
To Access
Press and hold the A/M Key and the Display Key for more than
1 second.
To Return to the Main PV/SP Display from the
Press and hold the A/M Key and the Display Key for more than
1 second.
To Access
Press and hold the A/M Key for more than 1 second.
Note:
To switch parameters within a mode, use the Display Key.
Press the display key for less than one second to move between
parameters.
1. In Level 0 mode, Level 1 mode, and Level 2 mode:
2. In Setup mode, Expansion mode, Option mode,
3. Option Mode will be accessible only when an option
The controller will maintain control of the process.
and Calibration mode: Control of the process is not
maintained. The outputs are inactive.
board is installed in the controller.