SDV-DH6 AC100/110

Manufacturer Part Number
SDV-DH6 AC100/110
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheet

Specifications of SDV-DH6 AC100/110

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
AC100/110 SDVDH6 SDVDH6AC100/110
■ Ratings
Note: The impedance value is a reference value; actual values may vary.
■ Characteristics
Note: Overvoltage:
Allowable continuous
input overvoltage range
Input impedance
Control output
Power consumption
Ambient temperature
Control supply voltage
(see note)
Operating value
Setting error
Operating time
Influence of temperature
Influence of control power
Influence of frequency
(Input frequency changed
from 10 to 500 Hz for AC in-
put)
Influence of waveform
(For commercial frequency,
single-phase, full-wave AC
input)
Insulation resistance
Dielectric strength
Impulse withstand voltage
Vibration resistance
Shock resistance
Weight
Undervoltage: Operation when voltage is changed from 120% to 80% of the operating value.
Item
Item
Operation when voltage is changed from 80% to 120% of the operating value.
±10 VDC
1 kΩ
SPDT
Rated load: 5 A at 220 VAC (cosφ = 1),
Max. contact voltage:
Max. contact current:
Max. switching capacity: 1,100 VA (cosφ = 1), 120 W (cosφ = 1),
DC: 5 W max.; AC: 5 VA max.
–10 to 55°C (with no icing)
24, 48, 100/110, 125, 200/220 VDC; DC operating voltage range: 80% to 130% of control power supply
100/110/120, 200/220/240 VAC (50/60 Hz); AC operating voltage range: 85% to 110% of control power supply
SDV-FL@
100% operation for voltage setting
Operating value: ±2% of operating value
Reset value: ±7% of reset value
0.5 s max. (see note)
0 to 40°C:
±2% max. of operating value
(SDV-FL (operating value range: 4 to 12 mV)
±4% max. of operating value)
–10 to 0°C, 40 to 55°C:
±4% max. of operating value
(SDV-FL (operating value range: 4 to 12 mV)
±8% max. of operating value)
±1% max. of operating value
DC operating voltage range: 80% to 130%
AC operating voltage range: 85% to 110%
±1% max. of operating value
±3% max. of operating value
10 MΩ min. (at 500 VDC) between the entire electric circuitry and external case, and between the input terminal
and power terminal
2,000 VAC for 1 min between the entire electric circuitry and external case, and between the input terminal and
power terminal
±1.2 x 50 μs, 4,500 V between the entire electric circuitry and external case
±1.2 x 50 μs, 3,000 V between power terminals
Destruction: 10 to 25 Hz, 2-mm double amplitude (2G max.) for 2 hrs each in 3 directions
Malfunction: 16.7 Hz, 1-mm double amplitude for 10 min each in 3 directions
Destruction: 294 m/s
Malfunction: 98 m/s
Approx. 290 g
(This is the ratio for the setting value.)
(This is the ratio for the setting value.)
5 A at 24 VDC (cosφ = 1),
2 A at 220 VAC (cosφ = 0.4),
2 A at 24 VDC (L/R = 7 ms)
SDV-F@@
±150 VDC
150 VAC
50 kΩ
5 A
250 VAC, 125 VDC
440 VA (cosφ = 0.4), 48 W (L/R = 7 ms)
SDV-FM@
2
2
(10G)
(30G)
Approx. 350 g
±350 VDC
(±500 VDC for 1 min)
350 VAC
(500 VAC for 1 min)
2,500 kΩ
SDV-FH@/FH@T
SDV-FH@T
±150 VDC
150 VAC
50 kΩ
SPST-NO and SPST-NC
±2% of intermediate voltage of dead band,
±1% of dead band voltage
0 to 40°C:
±2% max. of dead band voltage
–10 to 0°C, 40 to 55°C:
±4% max. of dead band voltage
±1% max. of dead band voltage
DC operating voltage range: 80% to 130%
AC operating voltage range: 85% to 110%
±1% max. of dead band voltage
±3% max. of dead band voltage
Approx. 310 g
SDV-DM@
SDV-D@@
±350 VDC
(±500 VDC for 1 min)
350 VAC
(500 VAC for 1 min)
2,500 kΩ
SDV-DH@
SDV
4